MODBUS(R) STANDARD FUNCTIONS
4.1 MODBUS(R) Standard Function Support List
4
- 4
1
O
VER
VIE
W
2
SYS
T
E
M
CO
NF
IG
U
R
A
T
IO
N
3
S
P
E
CIFICA
TI
ONS
4
MODB
US
(R)
S
TAN
DAR
D
FUN
C
TIO
N
S
5
FUNC
TI
ON
6
PR
E
-O
PER
A
T
ION
AL
P
R
OCED
URE
S A
ND
SE
TTINGS
7
P
A
RA
MET
E
R S
E
TTI
N
G
8
UTIL
ITY P
A
CK
AGE
(G
X Co
nf
ig
u
rat
o
r-M
B)
* 1 The slave function of the QJ71MB91 does not support this function.
(
Remark
The usable functions are limited when the QJ71MB91 is installed to a
MELSECNET/H remote I/O station.(
Table 4.1 MODBUS
standard function support list (continued)
Function
code
(Sub code)
Sub-function
code
Function
Description
Accessible
devices per
message
Broadcast Reference
16
-
Write multiple registers
Writes values to multiple holding
registers.
1 to
123 points
17
-
Report slave ID
Acquires the information of the slave
(QJ71MB91) mounted station into the
master.
-
20(6)
-
Read file record
Reads values of one or more extended
file registers.
1 to
124 points
21(6)
-
Write file record
Writes values to one or more extended
file registers.
1 to
122 points
22
-
Mask write register
Masks the values stored in a single
holding register with AND or OR and
writes the value.
1 point
23
-
Read/Write multiple
registers
Reads from or writes to multiple holding
registers.
Read:
1 to
125 points
Write:
1 to
121 points
24
*1
-
Read FIFO queue
Reads values from the holding
registers in FIFO queue structure.
-
-
-
43
*1
-
Read device
identification
Reads the module identification
information of the slave.
-
-
-