9
PROGRAMMING
9.3 Program Examples for Use in MELSECNET/H Remote I/O Network
9.3.2 MODBUS(R) device assignment parameters
9
- 38
9
P
R
OGRAM
M
ING
10
D
E
DICA
TED
INSTRUC
TI
ONS
11
TR
O
U
BLE
S
HOOTING
A
P
P
E
NDICE
S
INDE
X
(2) Communications
In the program example shown in this section, the following MODBUS device
assignment parameters are set for the setting target , QJ71MB91.
(a) MODBUS device assignment parameter assignment diagram
Figure 9.41 MODBUS
device assignment parameter settings
R
Output (Y)
Coil
000001
Y0
Y100
Y2FF
Y1FFF
065536
300001
303500
D3500
D8999
D12287
365536
308999
400001
401024
465536
MELSECNET/H remote I/O
station device
000512
512 points
Data register (D)
5500 points
D0
QJ71MB91 buffer memory
User free area
5000
H
5500
H
58FF
H
5FFF
H
1024 points
MODBUS device
512 points
5500 points
Holding register
Input register
1024 points