(2) Count range
Counting is performed up to FFFF
H
.
Counting is stopped when the count reaches FFFF
H
.
To continue counting, clear the diagnostic counter.
(
(3) Clearing the diagnostic counters
The diagnostic counters can be cleared by any of the following methods:
(a) Diagnostic counters for Master function (
• Power OFF
ON
• Resetting the programmable controller CPU
(b) Diagnostic counters for Slave function (
• When receiving the Clear Counters and Diagnostic Register
*1
(
• When receiving the Restart communications option
*1
(
• When receiving the Clear Overrun Counter and Flag
*2
(
• Clearing the buffer memory to "0" by sequence program
• Power OFF
ON
• By resetting the programmable controller CPU
* 1 The Message discard count, Data discard count and Failed transmission count are not cleared.
* 2 Only the Character overrun error count is cleared.
(4) Cautions
Diagnostic counters are not cleared while the QJ71MB91 is sending data.
Use the values of the diagnostic counters for checking the communication status.