119
-
'10 • SR-T-091
'09•SRK-DB-087D
(d) Cooling low outdoor air temperature protective control
1) Operating conditions:
2) Detail of operation:
C
D
A
B
OFF
E
F
Upper limit 50 rps
Lower limit 44 rps
ON
ON
Upper limit 50 rps
Lower limit 50 rps
ON
Upper limit 60 rps
Lower limit 30 rps
Outdoor air temperature.(°C)
3) Reset conditions:
(e) Heating high pressure control
1) Purpose:
2) Detector:
3) Detail of operation:
A
B
C
D
Indoor heat exchanger temperature(°C)
4rps
(1)
8rps
(2)
8rps
(2)
4rps
(1)
0rps
After lapse of 20 sec. or over
(3)
After lapse of 20 sec. or over
(3)
After lapse of 20 sec. or over
(3)
lower limit
speed 30(23) rps
(Example) Fuzzy
Temperature list
Models 20 ~ 35
A
B
C
D
RPSmin < 50
50 <= RPSmin < 91
91 <= RPSmin < 97
97 <= RPSmin < 100
100 <= RPSmin < 115
115 <= RPSmin
First time
Since the
seconds times
Outdoor air temperature (˚C)
A
B
C
D
E
F
a)
b)
a)
b)
than 50 <44> (30) rps, the speed is kept to 50 <44> (30) rps. However, when the thermo becomes OFF,the speed is
(Models 20 ~ 35)
First time
Since the
second times
Outdoor air temperature (˚C)
A
B
C
D
(Model 50)
(model 50 : 9ºC or 10ºC)
9
16
19
10
Note (1) Value in ( ) are for the model 50.
'09•SRK-DB-087D
(12)
ޓ
Protective control function
(a) Frost prevention control
1) Operating conditions
2) Detail of anti-frost operation
3) Reset conditions:
Indoor heat exchanger
temperature (ºC)
2.5
5
8
0 rps
Lower
limit
speed
compressor
command
speed
(b) Cooling overload protective control
1) Operating conditions:
2) Detail of operation
3) Reset conditions:
(c) Cooling high pressure control
1) Purpose:
2) Detector:
3) Detail of operation:
53
58
63
Outdoor heat exchanger temperature (°C)
6rps
(1)
6rps
(1)
0rps
After lapse of 30 sec. or over
(3)
After lapse of 30 sec. or over
(3)
After lapse of 30 sec. or over
(3)
lower limit
speed 30 (model 50 : 29) rps
(Example) Fuzzy
Indoor heat exchanger
temperature
Item
5°C or lower
2.5°C or lower
Lower limit of compressor command speed
Indoor fan
Outdoor fan
4-way valve
Item
SRK20~35ZJ-S
SRK50ZJ-S
Outdoor air temperature
Lower limit speed
Model
a)
b)
a)
b)
a)
b)
a)
b)
(model 50 : 23 rps)
more, or 47ºC or more (model 50 : 41ºC or more) with the compressor running, the lower limit
41°C or more
29 rps
The lower limit of compressor command speed is set to 30 or 40 (model 50 : 29) rps and even if the calculated result
becomes lower than that after fuzzy calculation, the speed is kept to 30 or 40 (model 50 : 29) rps. However, when the
thermo becomes OFF, the speed is reduced to 0 rps.
'09•SRK-DB-087D
(b)
1)
2)
3)
(c)
(d)
27.5
25.5
18.0
18
30
(10)
ޓ
Outline of cooling operation
(a)
ޓ
Operation of major functional components in Cooling mode
(b) Detail of control in each mode (Pattern)
1) Fuzzy operation
ON
OFF
OFF
OFF
OFF
OFF
ON
OFF
(few minutes ON)
OFF
(few minutes ON)
ON
ON
OFF
Thermostat ON
Thermostat OFF
Failure
Cooling
Compressor
Indoor fan motor
Outdoor fan motor
4-way valve
20~98rps
20~98rps
20~58rps
20~38rps
SRK35ZJ-S
23~96rps
23~96rps
23~62rps
23~38rps
SRK50ZJ-S
20~74rps
20~74rps
20~55rps
20~34rps
SRK25ZJ-S
20~66rps
20~66rps
20~44rps
20~30rps
SRK20ZJ-S
Model
Fan speed
Auto
MED
HI
LO
(11)
ޓ
Outline of automatic operation
(a) Determination of operation mode
Heating
Dehumidifying
Cooling
Indoor air temperature (˚C)
Outdoor air temperature (˚C)
Signals of wireless remote controller (Display)
–6
–5
–4
–3
–2
–1
±
0
+1
+2
+3
+4
+5
+6
Setting
temperature
Cooling
Dehumidifying
Heating
A
When both the indoor and the outdoor air temperatures are in the range “A”, cooling or heating is switched depending on
the difference between the setting temperature and the indoor air temperature.
When the operation mode has been judged following the change of setting temperature with the remote controller, the hourly
judgment of operation mode is cancelled.
Summary of Contents for SRK60ZJX-S
Page 85: ... 84 10 SR T 091 4 Ceiling cassette 4way compact type FDTC ...
Page 89: ... 88 10 SR T 091 a PJA012D783 ...
Page 189: ... 188 10 SR T 091 09 SRK DB 087D Service data record form 182 ...
Page 267: ... 266 10 SR T 091 12 5 Super link E board SC ADNA E F SL2NA E and SL3N AE BE to control ...
Page 268: ... 267 10 SR T 091 ...