'10 • SR-T-091
E5
Communication error during operation
Keeps flashing
2
times flash
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Has the remote
controller LCD returned to
normal state?
YES
NO
Is the
connection of signal
wires at the outdoor unit
side OK?
Is the
connection of signal
wires between indoor-outdoor
units OK?
Note (1) Inspect faulty connections (disconnection,
looseness) on the outdoor unit terminal block.
Power reset
Note (2) Check for faulty connection or breakage of
signal wires between indoor-outdoor units.
YES
NO
YES
NO
Repair signal wires.
Repair signal wires.
Defective outdoor PCB
(Defective network
communication circuit)
➞
Replace.
Unit is normal.
(Malfunction by temporary
noise, etc.)
2. Error detection method
When normal communication
between indoor and outdoor
unit is interrupted for more than
2 minutes.
3. Condition of Error displayed
Same as above is detected
during operation.
4. Presumable cause
• Unit No. setting error
• Broken remote controller wire
• Faulty remote controller wire
connection
• Faulty outdoor PCB
Note:
Error code
Remote controller:
LED
Green
Red
Indoor
Content
Summary of Contents for SRK60ZJX-S
Page 85: ... 84 10 SR T 091 4 Ceiling cassette 4way compact type FDTC ...
Page 89: ... 88 10 SR T 091 a PJA012D783 ...
Page 189: ... 188 10 SR T 091 09 SRK DB 087D Service data record form 182 ...
Page 267: ... 266 10 SR T 091 12 5 Super link E board SC ADNA E F SL2NA E and SL3N AE BE to control ...
Page 268: ... 267 10 SR T 091 ...