176
-
'10 • SR-T-091
(k) Outdoor unit failure
This is a function for determining when there is trouble with the outdoor unit during air conditioning.
The compressor is stopped if any one of the following in item 1), 2) is satisfied. Once the unit is stopped by this function, it is not
restarted.
1) When the input current is measured at 1 A or less for 3 continuous minutes or more.
2) If the outdoor unit sends a 0 rps signal to the indoor unit 3 times or more within 20 minutes of the power being turned on.
(l)
Rotor lock
If the motor for the compressor does not turn after it has been started, it is determined that a compressor lock has occurred and
the compressor is stopped.
(m) Outdoor fan motor protection
If the outdoor fan motor has operated at 75 rpm or under for more than 30 seconds, the compressor and fan motor are stopped.
(n) Outdoor fan control at low outdoor temperature
◆
Cooling
1) Operating conditions:
When the outdoor air temperature (TH2) is 22ºC or lower continues for 30 seconds while the
compressor command speed is other than 0 rps.
2) Detail of operation:
After the outdoor fan operates at A speed for 60 seconds; the corresponding outdoor heat
exchanger temperature shall implement the following controls.
Outdoor temperature > 10˚C
Outdoor temperature <= 10˚C
2nd speed
Outdoor fan
1st speed
¡
Value of A
a) Outdoor heat exchanger temperature =< 21ºC
After the outdoor fan speed drops (down) to 1 speed for 60 seconds; if the outdoor heat exchanger temperature is
lower than 21ºC
, gradually reduce the outdoor fan speed by 1 speed. (Lower limit 1st speed)
b) 21ºC < Outdoor heat exchanger temperature =< 38ºC
After the outdoor fan speed maintains at A speed for 20 seconds; if the outdoor heat exchanger temperature is 21ºC~
38ºC, maintain outdoor fan speed.
c) Outdoor heat exchanger tempeature > 38ºC
After the outdoor fan speed rises (up) to 1 speed for 60 seconds; if the outdoor heat exchanger temperature is higher
than 38ºC, gradually increase outdoor fan speed by 1 speed. (Upper limit 3rd speed)
3) Reset conditions:
When either of the following conditions is satisfied
a) The outdoor air temperature (TH2) is 25ºC or higher.
b) The compressor command speed is 0 rps.
◆
Heating
1) Operating conditions:
When the outdoor air temperature (TH2) is 4ºC or lower continues for 30 seconds while the
compressor command speed is other than 0 rps.
2) Detail of operation:
The outdoor fan is stepped up by 2 speed step at each 20 seconds. (Upper limit 8th speed)
3) Reset conditions:
When either of the following conditions is satisfied
a) The outdoor air temperature (TH2) is 6ºC or higher.
b) The compressor command speed is 0 rps.
Summary of Contents for SRK60ZJX-S
Page 85: ... 84 10 SR T 091 4 Ceiling cassette 4way compact type FDTC ...
Page 89: ... 88 10 SR T 091 a PJA012D783 ...
Page 189: ... 188 10 SR T 091 09 SRK DB 087D Service data record form 182 ...
Page 267: ... 266 10 SR T 091 12 5 Super link E board SC ADNA E F SL2NA E and SL3N AE BE to control ...
Page 268: ... 267 10 SR T 091 ...