(6) Number of parameters that can be set in GX Configurator-DN
When multiple intelligent function modules are mounted, the number of
parameter settings must not exceed the following limit.
When intelligent function modules are
installed to:
Maximum number of parameter settings
Initial setting
Auto refresh setting
Q00J/Q00/Q01CPU 512
256
Q02/Q02H/Q06H/Q12H/Q25HCPU 512
256
Q02PH/Q06PH/Q12PH/Q25PHCPU 512
256
Q00UJ/Q00U/Q01UCPU 512
256
Q02UCPU 2048
1024
Q03UD/Q04UDH/Q06UDH/Q10UDH/
Q13UDH/Q20UDH/Q26UDH/Q03UDE/
Q04UDEH/Q06UDEH/Q10UDEH/
Q13UDEH/Q20UDEH/Q26UDEHCPU
4096 2048
CPU modules other than listed above
Not available
Not available
For example, if multiple intelligent function modules are installed to the
Q25HCPU, configure the settings in GX Configurator so that the number of
parameter settings for all the intelligent function modules does not exceed the
limit of the Q25HCPU. Calculate the total number of parameter settings
separately for the initial setting and for the auto refresh setting.
The number of parameters that can be set for one module in GX Configurator-DN
is as shown below.
Target module
Initial setting
Auto refresh setting
QJ71DN91
0 (Not used)
18 (Max.)
Example) Counting the number of parameter settings in Auto refresh setting
This one row is counted as one setting.
Blank rows are not counted.
Count up all the setting items on this
screen, and add the total to the number
of settings for other intelligent
function modules to get a grand total.
(7) Writing parameters via the network
The QJ71DN91 does not support writing of parameters via the network.