7 - 24 7 - 24
MELSEC-Q
7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
(2) When setting parameters manually
(a) Device list
Device Description
Reference
section
M10
Parameter Setting Command for Master Function
―
X01 I/O
Communicating
Y11
I/O Communication Request
D4 to D35
Parameters for Master Function (for 1st to 4th slave
nodes)
3.4.5
(b) Program example
Node No.=1, group 2 only server
Connection type = Polling
Input byte module = 1
Output byte module = 0
Input word module = 0
Output word module = 0
Input double-word module = 0
Output double-word module = 0
Expected packet rate
Default = 200ms
Watchdog timeout action
Default = Timeout
Production inhibit time
Default = 10ms
Node No.=2, group 2 only server
[1st slave node]
[2nd slave node]
Parameters for master function
Connection type = Polling
Input byte module = 0
Output byte module = 1
Input word module = 0
Output word module = 0
Input double-word module = 0
Output double-word module = 0
Expected packet rate
Default = 200ms
Watchdog timeout action
Default = Timeout
Production inhibit time
Default = 10ms