3 - 38 3 - 38
MELSEC-Q
3 SPECIFICATIONS
(3) I/O Address Area for Master Function (address: 0500
H
to 05FB
H
/1280 to 1531)
This area stores the start addresses and sizes (number of words) of Master
Function Receive Data (address: 0700
H
to 07FF
H
/1792 to 2047) and Master
Function Transmit Data (address: 0900
H
to 09FF
H
/2304 to 2559) for each node.
This area can be used to check the start address of each node.
0500
H
0501
H
0502
H
0503
H
0504
H
5FB
H
Input data start address of
1st slave node
Input data size of 1st slave
node (No. of words)
Output data start address of
1st slave node
Output data size of 1st slave
node (No. of words)
Input data start address of
2nd slave node
Output data size of 63rd slave
node (No. of words)
3.4.7 Link scan time area for master function
Link scan time values are stored in this area.
(1) Present Link Scan Time (address: 05FC
H
/1532)
The present link scan time is stored. (Unit: ms)
(2) Minimum Link Scan Time (address 05FD
H
/1533)
The minimum link scan time after power-on is stored. (Unit: ms)
(3) Maximum Link Scan Time (address 05FE
H
/1534)
The maximum link scan time after power-on is stored. (Unit: ms)