5 - 2 5 - 2
MELSEC-Q
5 SETUP AND PREPARATION
5.1.2 When using the slave function
Start
Perform hardware test. (Mode 9)
Set mode to 3, 4, or 5.
Set Request for Saving Parameters to Flash ROM
(Y17) to on to save parameters to flash ROM.
Operation
Use GX Configurator-DN?
Parameters for slave function (See Section 8.2.1 (1).)
Set parameters for slave function.
Not needed unless I/O points for slave function are
changed.
Saving parameters to flash ROM (See Section 8.2.1 (2).)
Save parameters to flash ROM.
Parameters for slave function (See Section 8.2.2 (1).)
Create sequence program for setting parameters for
slave function. Not needed unless I/O points for slave
function are changed.
Saving parameters to flash ROM (See Section 8.2.2 (2).)
Create sequence program for saving parameters to
flash ROM.
Refresh setting (See Section 8.3.1.)
Configure auto refresh settings. Write intelligent
function module parameters to CPU module.
Refresh setting (See Section 8.3.2.)
Create sequence program for refresh.
Test run
Use
Not use
Create sequence program for control. After writing it to
programmable controller, reset CPU module.
OK
Failed
OK
Programming for control (See Section 8.3.1.)
Create sequence program for control. After writing it to
programmable controller, reset CPU module.
Programming for control (See Section 8.3.2.)
Set auto communication start setting. Not needed when starting
I/O communication by I/O Communication Request (Y11).
Auto communication start setting (See Section 8.2.2 (2).)
Create sequence program for auto communication start
setting. Not needed when starting I/O communication
by I/O Communication Request (Y11).
Auto communication start setting (See Section 8.2.1 (1).)
Set node No.
(See Section 5.4.)
(See Section 5.3.2.)
(See Section 5.3.3.)
(See Section 5.5.)
Connect DeviceNet cable to QJ71DN91.
Test run
Failed
5