108
Check of HPS
Infinity
0
Ω
Yes
No
1. Disconnect the connector CN681.
2. Check the resistance of HPS 1 minute after the outdoor unit power supply was turned OFF.
Check the resistance between
each terminal.
Reconnect CN681.
Turn ON the power supply to the indoor and outdoor units.
3 minutes later, start EMERGENCY OPERATION.
Is HPS protection displayed
immediately after compressor
starts?
Replace HPS.
Replace the electronic control P.C. board, control
P.C. board or the outdoor control P.C. board.
Normal
• When the operation frequency does not go up from lowest frequency.
MXZ-3C68/4C71/4C80/5C100/6C120/6C122VA
MXZ-4C80/5C100VA2
MXZ-3C/4C/5C
MXZ-6C120
MXZ-6C122
CN681
Electronic
control P.C. board
Control P.C. board
Outdoor control
P.C. board
OBH584G