109
The other cases
Indoor unit does not operate. (different operating models in multi system)
• When you try to run two indoor units simultaneously, one for cooling and the other for heating, the unit which transmits signal
to the outdoor unit first decides the operation mode.
• When the above situation occurs, set all the indoor units to the same mode, turn OFF the indoor units, then turn them back
ON.
• Though the top of the indoor unit sometimes gets warm, this does not mean malfunction. The reason is that the refrigerant
gas continuously flows into the indoor unit even while it is not operating.
Check of bus-bar voltage
•Check the voltage of power supply.
•Con
fi
rm outdoor unit failure mode
recall function. (Refer to 11-2.2.)
Blink 5 times
Con
fi
rm LED1 indication lamp on the
electronic control P.C. board.
Replace the power board.
Blink 9 times
Replace the electronic con-
trol P.C. board.
Turn OFF power supply before removing P.C. board.
Con
fi
rm LED1 indication lamp
on the electronic control P.C.
board.
Turn ON power supply.
Start operation.
Blink 6 times
Replace the electronic control
P.C. board .
Lighting
Replace the electronic
control P.C. board.
Blink 9 times
Replace the power board.
Con
fi
rm LED1 indication lamp
on the electronic control P.C.
board.
Turn ON power supply.
Start operation.
Normal
Lighting
Lighting
MXZ-3C/4C/5C
OBH584G
Summary of Contents for MXZ-2C30VA
Page 24: ...24 WIRING DIAGRAM 6 MXZ 2C30VA MXZ 2C40VA MXZ 2C52VA OBH584G ...
Page 25: ...25 MXZ 3C54VA OBH584G ...
Page 26: ...26 MXZ 3C68VA OBH584G ...
Page 27: ...27 MXZ 4C71VA OBH584G ...
Page 28: ...28 MXZ 4C80VA OBH584G ...
Page 29: ...29 MXZ 4C80VA2 OBH584G ...
Page 30: ...30 MXZ 5C100VA OBH584G ...
Page 31: ...31 MXZ 5C100VA2 OBH584G ...
Page 32: ...32 MXZ 6C120VA E1 OBH584G ...
Page 33: ...33 MXZ 6C120VA E2 OBH584G ...
Page 34: ...34 MXZ 6C122VA E1 OBH584G ...
Page 35: ...35 MXZ 6C122VA ER1 OBH584G ...
Page 36: ...36 MXZ 6C122VA E2 OBH584G ...
Page 37: ...37 MXZ 6C122VA ER2 OBH584G ...