39
Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the
tables
below.
UNIT: mm (inch)
Piping length each indoor unit (a, b)
20m
Total piping length (a+b)
30m
Bending point for each unit
20
Total bending point
30
MXZ-2C40VA
MAX REFRIGERANT PIPING LENGTH
a
b
Outdoor
unit
Indoor
units
15m
10m
15m
Refrigerant piping length (one way, 2 unit total)
Calculation : Xg = 20 g/m x (Refrigerant piping length (m) - 20)
Outdoor unit
precharged
(g)
30m
200
20m
0
1,300
Max.
Height
difference
Outdoor unit union diameter
For
Indoor unit A
Liquid
6.35(1/4)
Gas
9.52(3/8)
Indoor unit B
Liquid
6.35(1/4)
Gas
9.52(3/8)
Stop valve
(with strainer #100)
LEV A
LEV B
Compressor
Muffler
4-way valve
Indoor unit
B
Indoor unit
A
Indoor unit
A
Indoor unit
B
Capillary tube
Capillary tube
Stop valve
(with strainer #100)
R.V. coil
OFF
ON
Refrigerant flow in cooling
Refrigerant flow in heating
Discharge
temperature
thermistor RT62
Stop valve
(with service port)
Stop valve
(with service port)
Defrost
thermistor
RT61
Distributor
Capillary tube
Strainer
#100
Ambient
temperature
thermistor
RT65
Outdoor heat
exchanger
temperature
thermistor
RT68
FAN-OUT
HEX-OUT
Sub muffler
It is irrelevant which unit is higher.
ADDITIONAL REFRIGERANT CHARGE
OBH584G
Summary of Contents for MXZ-2C30VA
Page 24: ...24 WIRING DIAGRAM 6 MXZ 2C30VA MXZ 2C40VA MXZ 2C52VA OBH584G ...
Page 25: ...25 MXZ 3C54VA OBH584G ...
Page 26: ...26 MXZ 3C68VA OBH584G ...
Page 27: ...27 MXZ 4C71VA OBH584G ...
Page 28: ...28 MXZ 4C80VA OBH584G ...
Page 29: ...29 MXZ 4C80VA2 OBH584G ...
Page 30: ...30 MXZ 5C100VA OBH584G ...
Page 31: ...31 MXZ 5C100VA2 OBH584G ...
Page 32: ...32 MXZ 6C120VA E1 OBH584G ...
Page 33: ...33 MXZ 6C120VA E2 OBH584G ...
Page 34: ...34 MXZ 6C122VA E1 OBH584G ...
Page 35: ...35 MXZ 6C122VA ER1 OBH584G ...
Page 36: ...36 MXZ 6C122VA E2 OBH584G ...
Page 37: ...37 MXZ 6C122VA ER2 OBH584G ...