95
Primary current protection
Secondary current protection
High-pressure protection
Defrosting in cooling
3 times
Lighted
Discharge temperature
protection
4 times
Lighted
Low discharge
temperature protection
• Check the refrigerant circuit and the refrigerant amount.
• Refer to 11-6. "Check of LEV".
• Refer to 11-6. "Check of outdoor thermistors".
• Refer to 11-6. "Check of LEV".
• Check the refrigerant circuit and the refrigerant amount.
5 times
Lighted
Cooling high-pressure
protection
This symptom does not mean any abnormality of the
product, but check the following points.
• Check the indoor filters are not clogged.
• Check there is sufficient refrigerant.
• Check the indoor/outdoor unit air circulation is not
short cycling.
-
-
These symptoms do not mean any abnormality of the
product, but check the following points.
• Check the indoor filters are not clogged.
• Check there is sufficient refrigerant.
• Check the indoor/outdoor unit air circulation is not
short cycling.
Twice
Lighted
Once
Lighted
The outdoor heat exchanger temperature exceeds 58°C during operation.
9 times
Lighted
Inverter check mode
Lighted
Lighted
Normal
The unit is operated with emergency operation switch.
-
The primary current exceeds 15 A
(MXZ-3C54/3C68/4C71VA)
/
17 A
(MXZ-4C80VA, 4C80VA2)
/18 A
(MXZ-5C100VA, 5C100VA2)
.
The current of the compressor exceeds 12 A (
MXZ-3C54VA
) /12.5A
(
MXZ-3C68/4C71VA
) /10 A (
MXZ-4C80/5C100VA, 4C80/5C100VA2
).
The indoor gas pipe temperature exceeds 45°C during heating.
The indoor gas pipe temperature falls 3°C or below during cooling.
The discharge temperature exceeds 100°C during operation.
The frequency of the compressor is kept 80 Hz or more and the discharge
temperature is kept under 50°C (cooling) /40°C (heating) for more than
40 minutes.
Outdoor electronic control P.C. board (Parts side)
LED2 LED1
Lighting
LED1 LED2
Lighting
MXZ-3C54/3C68/4C71VA
MXZ-4C80/5C100VA
LED1(Red) LED2(Yellow)
Abnormal point / Condition
Remedy
Indication
Condition
No.
20
21
22
23
24
25
26
Outdoor unit
operates
normally.
Outdoor unit
operates.
Symptom
The flashing frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the flashing frequency is “2”.
ON
OFF
2.5-second OFF
2.5-second OFF
0.5-second ON
0.5-second ON
NOTE 1. The location of LED is illustrated at the right figure. Refer to 11-7.2.
2. LED is lighted during normal operation.
OBH584G
Summary of Contents for MXZ-2C30VA
Page 24: ...24 WIRING DIAGRAM 6 MXZ 2C30VA MXZ 2C40VA MXZ 2C52VA OBH584G ...
Page 25: ...25 MXZ 3C54VA OBH584G ...
Page 26: ...26 MXZ 3C68VA OBH584G ...
Page 27: ...27 MXZ 4C71VA OBH584G ...
Page 28: ...28 MXZ 4C80VA OBH584G ...
Page 29: ...29 MXZ 4C80VA2 OBH584G ...
Page 30: ...30 MXZ 5C100VA OBH584G ...
Page 31: ...31 MXZ 5C100VA2 OBH584G ...
Page 32: ...32 MXZ 6C120VA E1 OBH584G ...
Page 33: ...33 MXZ 6C120VA E2 OBH584G ...
Page 34: ...34 MXZ 6C122VA E1 OBH584G ...
Page 35: ...35 MXZ 6C122VA ER1 OBH584G ...
Page 36: ...36 MXZ 6C122VA E2 OBH584G ...
Page 37: ...37 MXZ 6C122VA ER2 OBH584G ...