10-5. INCREASING MAXIMUM COMPRESSOR OPERATIONAL FREQUENCY AND FAN SPEED OF THE
OUTDOOR UNIT
<MXZ-4C80VA, MXZ-4C80VA2, MXZ-5C100VA, MXZ-5C100VA2>
10-6. CHANGING DEFROST FINISH TEMPERATURE AND HEAT OPERATION TIME
<MXZ-4C80VA, MXZ-4C80VA2, MXZ-5C100VA, MXZ-5C100VA2, MXZ-6C120VA, MXZ-6C122VA>
Compressor operational frequency and fan speed can be increased.
Capacity of the unit can be improved with this function.
NOTE:
Compressor operational frequency may not be increased under primary current restriction or high pressure protection.
Compressor operational frequency will not be increased when 1 or 2 indoor units are operating.
This function does not work when the function which lowers the operating noise of the outdoor unit is activated.
Noise level of the outdoor unit will increase (You may need to explain this to your customers.)
[How to increase maximum compressor operational frequency and fan speed]
Turn OFF the power supply for the air conditioner before making the setting.
Set the “3” of SW2 on the outdoor P.C. board to ON to enable this function.
Turn ON the power supply for the air conditioner.
ON
SW2
1 2 3 4 5 6
If defrosting operation starts more than necessary, the defrost finish temperature and heat operation time can be changed.
The number of defrosting operation and defrosting time can be reduced with this function.
[How to change defrost finish temperature and heat operation time]
Turn OFF the power supply for the air conditioner before making the setting.
Set the “1” of SW2 on the outdoor P.C. board to ON to enable this function.
Turn ON the power supply for the air conditioner.
ON
SW2
1 2 3 4 5 6
Defrost finish temperature (°C)
Heat operation time (min.)
Initial setting
4C/5C
10
31
6C
13
31
Changed
4C/5C/6C
5
40
10-7. CHANGING THE AMPERE LIMIT
<MXZ-4C80VA, MXZ-4C80VA2, MXZ-5C100VA, MXZ-5C100VA2, MXZ-6C120VA, MXZ-6C122VA>
With this function, you can change the current that flows in the
outdoor unit.
[How to change the ampere limit]
Turn OFF the power supply for the air conditioner
before making the setting.
Make the setting referring to the table on the right.
Turn ON the power supply for the air conditioner.
NOTE:
Use this function only when the amount of current exceeds
the allowed value.
SW2
MXZ-6C120VA
MXZ-6C122VA
MXZ-4C80VA
MXZ-4C80VA2
MXZ-5C100VA
MXZ-5C100VA2
ON
10.5A
ON
15.5A
ON
Initial setting
Full
20A
25A
OBH584G
Summary of Contents for MXZ-2C30VA
Page 24: ...24 WIRING DIAGRAM 6 MXZ 2C30VA MXZ 2C40VA MXZ 2C52VA OBH584G ...
Page 25: ...25 MXZ 3C54VA OBH584G ...
Page 26: ...26 MXZ 3C68VA OBH584G ...
Page 27: ...27 MXZ 4C71VA OBH584G ...
Page 28: ...28 MXZ 4C80VA OBH584G ...
Page 29: ...29 MXZ 4C80VA2 OBH584G ...
Page 30: ...30 MXZ 5C100VA OBH584G ...
Page 31: ...31 MXZ 5C100VA2 OBH584G ...
Page 32: ...32 MXZ 6C120VA E1 OBH584G ...
Page 33: ...33 MXZ 6C120VA E2 OBH584G ...
Page 34: ...34 MXZ 6C122VA E1 OBH584G ...
Page 35: ...35 MXZ 6C122VA ER1 OBH584G ...
Page 36: ...36 MXZ 6C122VA E2 OBH584G ...
Page 37: ...37 MXZ 6C122VA ER2 OBH584G ...