90
MXZ-6C
Upper or
left lamp of
OPERATION
INDICATOR
lamp (Indoor
unit)
Abnormal point
(Failure mode/protection)
LED indication
(Outdoor P.C. board)
Condition
Remedy
Indoor/
outdoor
unit failure
mode
recall
function
LED 1
LED 2
OFF
None (Normal)
Lighted
Lighted
2-time
fl
ash
Outdoor power system
Lighted
Lighted
Overcurrent protection cut-out operates
3 consecutive times, bus-bar voltage
protection cut-out operates 3 consecu-
tive times, or primary current protection
cut-out operates 3 consecutive times
within 1minute after the compressor
gets started.
• Check the connection of
the compressor connecting
wire.
• Refer to 11-6. How to
check inverter/compressor.
• Check the stop valve.
○
3-time
fl
ash
Discharge temperature thermis-
tor
Lighted
Once
Thermistor shorts or opens during
compressor running.
• Refer to 11-6. "Check of
outdoor thermistors".
○
Defrost thermistor
Lighted
Once
Ambient temperature thermistor
Lighted
Twice
Fin temperature thermistor
Lighted
3 times
• Replace the power board
(MXZ-6C120VA)
/outdoor pow-
er P.C. board
(MXZ-6C122VA)
.
P.C. board temperature thermis-
tor
Lighted
4 times
• Replace the power board
(MXZ-6C120VA)
/outdoor pow-
er P.C. board
(MXZ-6C122VA)
.
Outdoor heat exchanger tem-
perature thermistor
Lighted
9 times
• Refer to 11-6. "Check of
outdoor thermistors".
4-time
fl
ash
Overcurrent
Once
Not
lighted
40 A current
fl
ows into intelligent power
module.
• Reconnect compressor con-
nector.
• Refer to 11-6. "How to
check inverter/compressor".
• Check the stop valve.
—
Out-of-step protection
9 times
Not
lighted
Waveform of compressor current is dis-
torted.
• Refer to 11-6. " How to
check inverter/compressor.
5-time
fl
ash
Discharge temperature
Lighted
Lighted
Discharge temperature exceeds 114 °C
during operation.
Compressor can restart if discharge
temperature thermistor reads 100 °C or
less 3 minutes later.
• Check the refrigerant circuit
and the refrigerant amount.
• Refer to 11-6. "Check of
LEV".
—
6-time
fl
ash
High pressure
Lighted
Lighted
High-pressure is detected with the
high-pressure switch (HPS) during op-
eration.
• Check the refrigerant circuit
and the refrigerant amount.
• Check the stop valve.
—
The outdoor heat exchanger tempera-
ture exceeds 70 °C during cooling or
the indoor gas pipe temperature ex-
ceeds 70°C during heating.
7-time
fl
ash
Fin temperature
3 times
Not
lighted
The fin temperature exceeds
:
110 °C
(MXZ-6C120VC-
E1
)
/ 105°C
(MXZ-
6C120VC-
E2
, MXZ-6C122VC-
E1
) dur-
ing operation.
• Check around the outdoor
unit.
• Check the outdoor unit air
passage.
• Refer to 11-6. "Check of
outdoor fan motor".
—
P.C. board temperature
4 times
Not
lighted
The P.C. board temperature exceeds
95 °C during operation.
8-time
fl
ash
Outdoor fan motor
Lighted
Lighted The fan motor speed is 50 rpm or less
or 1500 rpm or more for 1 minute, or
the fan motor speed is 100 rpm or
less for 15 seconds when the outside
temperature is 20 °C or more.
• Refer to 11-6. "Check of
outdoor fan motor".
—
9-time
fl
ash
Nonvolatile memory data
Lighted
5 times
Nonvolatile memory data cannot be
read properly.
• Replace the control P.C. board
( M X Z - 6 C 1 2 0 VA )
/ o u t d o o r
control P.C. board
( M X Z -
6C122VA)
.
• Replace the power board
(MXZ-6C120VA)
/outdoor pow-
er P.C. board
(MXZ-6C122VA)
.
○
10-time
fl
ash
Discharge temperature
Lighted
Lighted
The frequency of the compressor is
kept 58Hz or more and the discharge
temperature is kept under 50 °C (cool-
ing)/40 °C (heating) for more than 40
minutes.
• Check the refrigerant circuit
and the refrigerant amount.
• Refer to 11-6. "Check of
LEV".
—
OBH584G
Summary of Contents for MXZ-2C30VA
Page 24: ...24 WIRING DIAGRAM 6 MXZ 2C30VA MXZ 2C40VA MXZ 2C52VA OBH584G ...
Page 25: ...25 MXZ 3C54VA OBH584G ...
Page 26: ...26 MXZ 3C68VA OBH584G ...
Page 27: ...27 MXZ 4C71VA OBH584G ...
Page 28: ...28 MXZ 4C80VA OBH584G ...
Page 29: ...29 MXZ 4C80VA2 OBH584G ...
Page 30: ...30 MXZ 5C100VA OBH584G ...
Page 31: ...31 MXZ 5C100VA2 OBH584G ...
Page 32: ...32 MXZ 6C120VA E1 OBH584G ...
Page 33: ...33 MXZ 6C120VA E2 OBH584G ...
Page 34: ...34 MXZ 6C122VA E1 OBH584G ...
Page 35: ...35 MXZ 6C122VA ER1 OBH584G ...
Page 36: ...36 MXZ 6C122VA E2 OBH584G ...
Page 37: ...37 MXZ 6C122VA ER2 OBH584G ...