93
-
-
9 times
Lighted
Inverter check mode
Lighted
Lighted
Normal
The connector of compressor is disconnected.
Inverter check mode starts.
-
5 times
Lighted
Cooling high-pressure
protection
This symptom does not mean any abnormality of the
product, but check the following points.
• Check if the indoor filters are clogged.
• Check if the refrigerant is short.
• Check if the indoor/outdoor unit air circulation is short
cycled.
The outdoor heat exchanger temperature exceeds 58°C during operation.
20
LED1(Red) LED2(Yellow)
Abnormal point / Condition
Remedy
Indication
Condition
No. Symptom
Outdoor unit
operates
normally.
21
22
Outdoor unit
operates.
Display P.C. board (Parts side)
Lighting
LED1 LED2
The flashing frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the flashing frequency is “2”.
ON
OFF
2.5-second OFF
2.5-second OFF
0.5-second ON
0.5-second ON
NOTE 1. The location of LED is illustrated at the right figure. Refer to 11-7.6.
2. LED is lighted during normal operation.
OBH584G
Summary of Contents for MXZ-2C30VA
Page 24: ...24 WIRING DIAGRAM 6 MXZ 2C30VA MXZ 2C40VA MXZ 2C52VA OBH584G ...
Page 25: ...25 MXZ 3C54VA OBH584G ...
Page 26: ...26 MXZ 3C68VA OBH584G ...
Page 27: ...27 MXZ 4C71VA OBH584G ...
Page 28: ...28 MXZ 4C80VA OBH584G ...
Page 29: ...29 MXZ 4C80VA2 OBH584G ...
Page 30: ...30 MXZ 5C100VA OBH584G ...
Page 31: ...31 MXZ 5C100VA2 OBH584G ...
Page 32: ...32 MXZ 6C120VA E1 OBH584G ...
Page 33: ...33 MXZ 6C120VA E2 OBH584G ...
Page 34: ...34 MXZ 6C122VA E1 OBH584G ...
Page 35: ...35 MXZ 6C122VA ER1 OBH584G ...
Page 36: ...36 MXZ 6C122VA E2 OBH584G ...
Page 37: ...37 MXZ 6C122VA ER2 OBH584G ...