72
Discharge temperature
thermistor
Purpose
Protection
Defrosting
Protection
Defrosting
Control
Control
Protection
Protection
Control
Compressor
LEV
Outdoor
fan motor
4-way
valve
Sensor
Defrost thermistor
Fin temperature
thermistor
Indoor pipe temperature
thermistor
Capacity code
Evaporation temperature
thermistor
Gas pipe temperature
thermistor
High pressure
switch
Actuator
Relation between main sensor and actuator.
10-19. Relation between main sensor and actuator
SERVICE FUNCTIONS
11
11-1. COMPULSORY DEFROSTING MODE FOR SERVICE
By short circuit of the connector JP607 and R853 on the outdoor deicer P.C. board, defrosting mode can be accom-
plished regardless of the defrost interval restriction. (Refer to page 96.)
Defrost thermistor RT61 must read below 27°F(MSH09TW,MSH12/15/17TN)/ 32°F(MSH09TW
-
,MSH12/15/17TN
-
). (Refer to page 73.)
U1
U1
MSH09TW
MSH12TN
MSH15TN
MSH17TN
MSH09TW -
MSH12TN -
MSH15TN -
MSH17TN -
U1
U1
U1
U1
MUH09TW
MUH12TN
MUH15TN
MUH17TN
MXZ30TN
MXZ30TN2
MUH09TW -
MUH12TN -
MUH15TN -
MUH17TN -
U1
U1
U1
U1
MUH09TW
MUH12TN
MUH15TN
MUH17TN
Model
Jumper wire
Change point
JPC
JPE
Defrost interval time changes from 40 minutes to 15minutes.
Defrost start temperature changes from 27˚F to 32˚F.
Defrost finish temperature changes from 38˚F to 50˚F.
11-2. CHANGE IN DEFROST SETTING
✳
MXZ30TN and MXZ30TN2 is not equipped with this function.
<MSH09TW, MSH12/15/17TN>
<JPC> When the JPC wire of the deicer P.C. board is cut, the defrost interval time is changed.
<JPE> When the JPE wire of the deicer P.C. board is cut, the defrost temperature is changed. (Refer to page 96.)
MUH12TN -
MUH15TN -
U2
U2
OB275--3.qxp 03.12.2 5:19 PM Page 72