100
RELAY OPERATION
MSH09TW
MSH12TN
MSH15TN
MSH17TN
MODE
THERMOSTAT
52C CONTACTOR
INDOOR FAN SPEED
COOL &
COOL mode
of I FEEL
CONTROL
DRY &
DRY mode
of I FEEL
CONTROL
HEAT &
HEAT mode
of I FEEL
CONTROL
ON
OFF
OFF
OFF
ON
ON
ON
OFF
ON
OFF
OFF for 2 min. after
unit starts operation.
Repeat of 8 min. ON/3min.
OFF operation or 2 min.
ON/3 min. OFF operation
Repeat of 4 min. OFF/
1 min. ON operation
AUTO or set speed
AUTO or set speed
AUTO or set speed links with 52C
contactor.
AUTO or set speed
OFF or Very Low speed
NOTE : Once the compressor is OFF, “3-minute time delay circuit” works at next start-up.
• COIL FROST PREVENTION
MODE
THERMOSTAT
52C CONTACTOR
INDOOR FAN SPEED
COOL &
COOL mode
of I FEEL
CONTROL
DRY &
DRY mode
of I FEEL
CONTROL
ON
OFF for 5 min. After
that, OFF is pro-
longed until indoor
coil thermistor reads
termination temper-
ature.
AUTO or set speed
AUTO or set speed
<MSH12/15/17>
Low speed when coil frost prevention
starts while COMPRESSOR OFF
2. SOLID STATE RELAY (INDOOR FAN MOTOR RELAY)
MSH12TN MSH15TN MSH17TN MSH12TN -
MSH15TN -
MSH17TN -
U1
U1
U1
Indoor fan speed
High
Med.
Low
Very Low
OFF
Relay turning ON
SR144
SR143
SR142
SR141
All fan relays are OFF.
MSH09TW -
MSH12TN -
MSH15TN -
MSH17TN -
U1
U1
U1
U1
1. COMPRESSOR CONTACTOR
• EACH MODE
OB275--4.qxp 03.12.2 5:22 PM Page 100