Check of indoor electronic control P.C. board
Check the both “parts side” and “pattern
side” of indoor electronic control P.C.
board visually.
Replace the fuse.
Is fuse (F11) blown?
Be sure to check both fuse
and varistor in any case.
Replace the fan
motor.
Replace the indoor
electronic control
P.C. board.
Is winding
resistance of
fan motor 0
"
?
Is winding
resistance of
vane motor 0
"
?
No
Yes
Replace the vane
motor.
No
Yes
Yes
Is varistor (NR11) burnt?
Replace the varistor.
Yes
Turn OFF the power supply.
Disconnect indoor fan motor connector CN211(MSH09
only) and vane motor connector CN151 from the indoor
electronic control P.C. board and turn ON the power supply.
No
No
Does the unit operate with the remote controller or
the OPERATION INDICATOR lamp light up
by pressing the EMERGENCY OPERATION switch?
Yes
No
Be sure to check both resistances.
Turn OFF the
power supply.
Turn OFF the
power supply.
The unit doesn’t operate with the remote controller.
Also, the OPERATION INDICATOR lamp doesn’t light up by pressing the EMERGENCY OPERATION switch.