77
MXZ30TN MXZ30TN2 only
Operation start
Check the outdoor unit
LED indicator
I
Check of power supply
See page 89.
• Indoor unit
serial signal
error
J
Check of
serial signal
See page 89.
• COOL or HEAT
operation only
K
Check of
R.V.coil
See page 90.
• When cooling,
room does not
cool.
M
Check of
inverter,
compressor
See page 91.
• When cooling, heat
exchanger of
non-operating indoor
unit frosts.
•When heating, non
operating indoor unit
gets warm.
L
Check of LEV
See page 91.
• When cooling,
dew drops in the
non-operating
indoor unit
Check of mis-
piping.
• When heating,
room does not get
warm.
M
Check of
inverter,compressor
See page 91.
Check mis-piping
Shortage of capacity
Refer to indicator list
See page 79, 80.
OFF
"
00
"
• Check the indoor unit with referring to the indoor unit service manual, and confirm that there is any problem in the indoor unit.
Then, check the outdoor unit with referring to this page.
Display other than "
00
"
OB275--3.qxp 03.12.2 5:19 PM Page 77