5 MODULE DEDICATED INSTRUCTION
5.4 Network Dedicated Instruction
Network parameter setting
G(P)_RLPASET
The following instruction can go in the dotted squares.
G_RLPASET, GP_RLPASET
■
Executing condition
■
Argument
*1 Local devices and file registers per program cannot be used as setting data.
Processing details
This instruction sets the network parameters to the master station and starts up the data link.
Instruction
Executing condition
G_RLPASET
GP_RLPASET
Input/output
argument
Name
Description
Data type
Input argument
EN
Executing condition
Bit
Un*
Start I/O number of the module
00 to FE: Higher two digits when expressing the I/O
number in three digits)
ANY16
s1
Variable that stores control data
Array of ANY16 [0..7]
s2
Variable that stores slave station setting data
Array of ANY16 [0..63]
s3
Variable that stores reserved station specification
data
Array of ANY16 [0..3]
s4
Variable that stores error invalid station
specification data
Array of ANY16 [0..3]
s5
Variable that stores send/receive and auto-refresh
buffer assignment data
Array of ANY16 [0..77]
Output argument
ENO
Execution result
Bit
d
Variable that turns ON upon completion of the
instruction
d[1] also turns ON at the time of error completion.
Array of bit [0..1]
Setting
data
Internal device
R, ZR
J
\
U
\G
Zn
Constant
Others
Bit
Word
Bit
Word
(s1)
(s2)
(s3)
(s4)
(s5)
(d)
CC-Link
Structured ladder/FBD
ST
G_RLPASET
EN
ENO
Un*
s1
s2
s3
s4
s5
d
G_RLPASET
(EN, Un*, s1, s2, s3, s4, s5, d);
ENO:=