5 MODULE DEDICATED INSTRUCTION
5.4 Network Dedicated Instruction
135
5
Setting data
Device
Item
Setting data
Setting
range
Setting
side
(s1)[0]
Execution/Error
completion type
Execution type (bit 0)
0000H,
0001H,
0080H,
0081H
User
■
Ethernet
0: Without arrival confirmation
• When the target station is on the same network
Completed when data are sent from the host station.
• When the target station is on another network
Completed when data reach to a relay station on the same network.
1: With arrival confirmation
Completed when data are written to the target station.
■
MELSECNET/HCC-Link IE
0: Without arrival confirmation
• When the target station is on the same network
Completed when data are sent from the host station.
• When the target station is on another network
Completed when data reach to a relay station on the same network.
1: With arrival confirmation
Completed when data are written to the target station.
When '0: Without arrival confirmation' is specified, even if writing to the target station is
completed abnormally in the following cases, the processing of the instruction in the
host station is completed normally.
• Communication itself was completed normally, although the sent data were
erroneous.
• Data could not be written to the target station because instructions from multiple
stations were executed to the same station. (An error code (F222H, E006H, E205H,
D202H, or D282H) is detected at the target station.)
b15
0
0
(2)
(1)
b7
b0
…
…
Execution source
Target station
Completed
Execution source
Target station
Completed
Relay station
Execution source
Target station
Completed
Relay station
Completed
Target station
Completed
Target station
Request source
Completed
Target station
Request source
Relay station
Completed
Target station
Request source
Relay station
Target station
Completed
Summary of Contents for MELSEC System Q
Page 1: ...MELSEC Q L Structured Programming Manual Special Instructions ...
Page 2: ......
Page 307: ...10 SFC CONTROL INSTRUCTION 10 2 SFC Transition Condition Comment Read 305 10 MEMO ...
Page 309: ...I 307 MEMO ...
Page 315: ......