5 MODULE DEDICATED INSTRUCTION
5.4 Network Dedicated Instruction
Setting parameter
G(P)_CCPASET
The following instruction can go in the dotted squares.
G_CCPASET, GP_CCPASET
■
Executing condition
■
Argument
*1 Local devices and file registers per program cannot be used as setting data.
Processing details
This instruction sets parameters for master/local module (master station).
Instruction
Executing condition
G_CCPASET
GP_CCPASET
Input/output
argument
Name
Description
Data type
Input argument
EN
Executing condition
Bit
Un*
Start I/O number of the module
(00 to FE: Higher two digits when expressing the I/
O number in three digits)
ANY16
s1
Variable that stores control data
Array of ANY16 [0..3]
s2
Start number of the host station's device that stores
network configuration setting data.
Array of ANY16 [0..599]
s3
Start number of the host station's device that stores
reserved station specification data.
Array of ANY16 [0..7]
s4
Start number of the host station's device that stores
error invalid station setting data.
Array of ANY16 [0..7]
Output argument
ENO
Execution result
Bit
d
Variable that turns ON upon completion of the
instruction
d[1] also turns ON at the time of error completion.
Array of Bit [0..1]
Setting
data
Internal device
R, ZR
J
\
U
\G
Zn
Constant
Others
Bit
Word
Bit
Word
(s1)
(s2)
(s3)
(s4)
(d)
CC IE F
ST
EN
ENO
Un*
d
s1
s2
s3
s4
G_CCPASET
G_CCPASET (EN, Un*, s1, s2, s3, s4, d);
ENO:=
Structured ladder/FBD