5 MODULE DEDICATED INSTRUCTION
5.4 Network Dedicated Instruction
*1 Data are stored only when 1 is set in bit 7 of Error completion type ((s)[0]).
Program example
The following program reads out data, which is sent from the station number 1 by the SEND instruction, from the channel 5 of
the station number 2 (host station) and stores the data to the devices from D770 to D773 of the station number 2 (host station)
when SB0034 turns ON.
For the SEND instruction, refer to the following section.
Message (user-specified data) communication
(s)[17]
Error-detected
station No.
Number of the station where an error was detected is stored. (However, when an
error was detected at the host station, the network number is not stored.)
Stored values are as follows.
• MELSECNET/H: 1 to 64
• Ethernet, CC-Link IE Controller Network: 1 to 120
• Master station in CC-Link IE Field Network: 125 (7DH)
• Local station or the intelligent device station in CC-Link IE Field Network: 1 to 120
System
Device
Item
Setting data
Setting
range
Setting side