76
5 MODULE DEDICATED INSTRUCTION
5.3 Serial Communication Instruction
Setting data
■
Registering the programmable controller CPU monitoring
Device
Item
Setting data
Setting
range
Setting side
(s2)[0]
Execution type
Specify '0'.
0
User
(s2)[1]
Completion status
The instruction completion status is stored.
0: Normal completion
Other than 0: Error completion (error code)
System
(s2)[2]
Request type
Specify the request.
2: Registration of programmable controller CPU
monitoring
2
User
(s2)[3]
Cycle time unit
Specify the unit of cycle time.
0: 100ms
1: Second
2: Minute
0 to 2
User
(s2)[4]
Cycle time
Specify the cycle time.
1H to FFFFH: Cycle time
1H to FFFFH
User
(s2)[5]
Programmable controller CPU monitoring function
Specify the monitoring function.
1: Constant cycle transmission
2: Condition agreement transmission
1,2
User
(s2)[6]
Programmable controller CPU monitoring
transmission method
Specify the transmission method.
0: Data transmission (device data, CPU error
information)
1: Notification
0, 1
User
(s2)[7]
Constant cycle
transmission
User frame output start pointer
Specify the start pointer of the table to which the user
frame number for constant cycle transmission is set.
0: No specification (at condition agreement
transmission and notification)
1 to 100: Start pointer
0, 1 to 100
User
(s2)[8]
Number of user frame
transmissions
Specify the number of user frame transmissions
(outputs) for constant cycle transmission.
0: No specification (at condition agreement
transmission and notification)
1 to 100: Number of transmissions
0, 1 to 100
User
(s2)[9]
Modem connection data No.
Specify the data number for modem function
connection when making notification in constant
cycle transmission.
0: No specification (at data transmission and
condition agreement transmission)
BB8H to BD5H: Connection data number (flash
ROM)
8001H to 801FH: Connection data number (buffer
memory)
0,
BB8H to
BD5H,
8001H to
801FH
User
(s2)[10]
Number of registered word blocks
Specify the number of blocks of the word device to
be monitored.
0 to 10
User
(s2)[11]
Number of registered bit blocks
Specify the number of blocks of the bit device to be
monitored.
0 to 10
User
(s2)[12]
Programmable controller CPU error monitoring
(programmable controller CPU status monitoring)
Specify whether to also execute programmable
controller CPU error monitoring.
0: Not monitored
1: Monitored
0, 1
User