50
1 FUNCTIONS
1.4 Diagnostic Function
■
When "Short Circuit Auto Clear enable/disable" is set to "Enable"
The following shows the operation of when the connection is recovered from the short circuit.
• The value of 'Output short-circuit detection status' (Un\G3088) changes from 1 (Short circuit detected) to 0 (Normal).
• 'Alarm flag' (X11) turns off.
• The ALM LED turns off.
Setting procedure
Set the following items from "Application setting".
• "Output short-circuit detection setting" (
Page 106 Output short-circuit detection setting)
• "Short Circuit Auto Clear enable/disable" (
Page 106 Output short-circuit detection automatic clear enable/disable)
[Navigation window]
[Parameter]
[Module Information]
Target module
[Module Parameter]
[Application
setting]
List of detectable conditions
For the places at which output short circuit can be detected and the detectable conditions, refer to the following.
Page 48 List of detectable conditions
: Performed by the output module with diagnostic functions.
ON
0
1
0
OFF
ALM LED
Short-circuit status
Normal
Short circuit
Normal
Off
On
Off
'Output short-circuit
detection status' (Un\G3088)
'Alarm flag'
(X11)