10 FUNCTIONS
10.4 Input Diagnostic Function
■
Double input discrepancy auto recovery enabled signal
When "Auto recovery settings after discrepancy error" is set to "Enable", 1 is stored in Double input discrepancy auto recovery
enabled signal (Un\G1032). For details on Double input discrepancy auto recovery enabled signal (Un\G1032), refer to the
following.
Page 214 Double input discrepancy auto recovery enabled signal
Double input discrepancy auto recovery enabled signal (Un\G1032) is a buffer memory area for monitoring.
Do not use it for safety programs.
■
Setting procedure
Set with "Auto recovery settings after discrepancy error".
[Navigation window]
[Parameter]
[Module Information]
Model
[Module Parameter]
[Application setting]
"Auto recovery settings after discrepancy error"
The "Auto recovery settings after discrepancy error" setting is effective only for input signals with "Redundant
input discrepancy detection settings" set to "Enabled" and "Redundant input discrepancy detection type" set
to "Discrepancy detection time specified". For input signals with values other than the above set, the value set
for "Auto recovery settings after discrepancy error" will be ignored.
Double input discrepancy detection state monitoring signal
Regardless of the setting of "Auto recovery settings after discrepancy error", the double input discrepancy detection state can
be monitored with Double input discrepancy detection state (Un\G1036). For details on Double input discrepancy detection
state (Un\G1036), refer to the following.
Page 214 Double input discrepancy detection state
Double input discrepancy detection state (Un\G1036) is a buffer memory area for monitoring. Do not use it for
safety programs.