12 MAINTENANCE AND INSPECTION
12
MAINTENANCE AND INSPECTION
This chapter describes inspection to be performed for using the I/O module with diagnostic functions in SIL2 mode.
Periodic inspection
Perform the following inspection one or two times in 6 months to a year. Perform it as well after equipment is transferred or
modified, or wiring is changed.
• Apply 6V to all input terminals of the input module with diagnostic functions and check that an input does not turn on.
For other inspection items, refer to the following.
MELSEC iQ-R Module Configuration Manual