6 SPECIFICATIONS
6.1 Performance Specifications
Output module with diagnostic functions
*1 Use an external power supply satisfying the following conditions.
An external power supply has the overvoltage protection function.
The output voltage does not exceed 35VDC when a single fault occurs.
• Immediately after power-off of the power supply module, if the input power source is applied to the power
supply module again, the output module with diagnostic functions may not start up. When applying the input
power source to the power supply module again, wait five seconds or more after the shut-off of the power,
and apply the power again.
• For the output module with diagnostic functions, connect a device with the response speed of 1ms or
longer. Connecting a device with the response speed shorter than 1ms can cause a malfunction of the
device.
Item
Specifications
Number of output points
16
Rated load voltage
24VDC (Allowable voltage range: 20.4 to 28.8VDC)
Maximum load current
0.5A/point, 5A/common
Maximum inrush current
Current is to be limited by the overload protection function.
Leakage current at OFF
0.3mA or lower
Maximum voltage drop at ON
1.0VDC (TYP.) 0.5A
Output response time
OFF
ON
0.5ms or less
ON
OFF
1.5ms or less
Control cycle time
2ms
Surge suppressor
Zener diode
Fuse
None
External power supply
Voltage
24VDC (Ripple ratio: Within 5%) (Allowable voltage range: 20.4 to 28.8VDC)
Current
87mA (at 24VDC)
Withstand voltage
510VACrms for one minute
Isolation resistance
10M
or more with isolation resistance tester
Noise immunity
Simulator noise 500Vp-p, noise width 1
s,
noise frequency 25 to 60Hz (noise simulator condition)
Protection degree
IP2X
Wiring method for common
16 points/common (common terminal: TB18)
Number of occupied I/O points
32 points (I/O assignment: Output 32 points)
Protection function
Overload protection
Limited current when detecting overcurrent: 1.0A or higher/point
Activated to each point. (
Overheat
protection
Activated to each point. (
External interface
18-point screw terminal block (M3
6 screw)
Internal current consumption (5VDC)
190mA (TYP. all points ON)
Weight
0.24kg