9.3. Configuration
The default IP address for all centralised controllers is 192.168.1.1 and subnet mask 255.255.255.0.
The default IP address for MelcoREMOTE is 192.168.1.2 and subnet mask 255.255.255.0.
When connecting Ethernet devices together each one needs to have a unique IP address.
9.3.1. PIN Codes
The following PIN codes must be entered to enable communication between the central controller and MelcoREMOTE.
Controller Type
PIN Code required
G-50 G50-WebMonitor
GB-50 GB50-Basic
AG-150 AG150-Basic
AE-200 / EW-50
(no PIN required)
The applicable centralised controller PIN code must be entered to enable communication with
MelcoREMOTE.
9.3.2. AE-200 / EW-50
The AE-200 and EW-50 controller has a setting called ‘
Old Model Compatibility Mode’
which needs to be set to ON for
correct operation with MelcoREMOTE. This setting can be accessed through the ‘
Initial Setting’
screen under the
‘
Advanced
’ tab or embedded webpage for the AE-200, for the EW-50 it must be changed through the embedded
webpage.
All AE-200 and EW-50 controllers must have their ‘Old Model Compatibility Mode’ setting set to ON for
correct operation with the MelcoREMOTE.