Page 8 of 52
1. Quick start guide
Step 1:
Mount the Procon MelcoREMOTE and power supply on suitable DIN rail and complete the wiring between the two.
Connect the 230VAC power supply but do not switch ON.
Step 2:
Connect the GPRS antenna or Ethernet cable, depending on the desired server connection method.
Step 3:
If required, connect the MelcoREMOTE to the Mitsubishi Centralised Controllers (e.g. AE-200) with Ethernet cable.
Step 4:
Connect all other required inputs, outputs and RS-485 devices (e.g. MelcoBEMS MINI (A1M) devices).
Step 5:
Switch ON the power supply and check the MelcoREMOTE produces a double beep and within 1 minute successfully
connects and synchronises with the server. After the synchronisation is complete the screen will show the message
‘Online’ or ‘Connected to server’, both of these indicate a successful connection has been made.
Please refer to the
Configuration and Commissioning
section for more information on the messages shown on the
screen.
Step 6:
The current readings of all configured I/Os can be viewed and checked using the screen, see section
Configuration and
Commissioning
for more details.
This section also describes the ‘toggle’ feature which can be used to temporarily switch the digital outputs ON/OFF for
testing purposes.