To connect a 4-20mA sensor that requires “loop” power:
-
Isolate the MelcoREMOTE supply.
-
Connect the positive (+) terminal on the sensor to the
RS-485 Port 1+
or
RS-485 Port 2+
terminal on the
MelcoREMOTE.
-
Connect the negative (-) terminal on the sensor to the required positive (+) configurable input terminal on
MelcoREMOTE (e.g.
IN01+
).
The maximum cable length for 4-20mA inputs is 1000m. This represents a cable loss of < 5V at 25mA.
8.2. Connecting Outputs
For connecting contactors (nominal 100mA coil) to digital outputs, the maximum cable length is 50 metres (16/0.2, tri-
rated cable). This represents a cable loss of <1V @ 80mA (typical contactor current).