Operating Instructions
»
ME96SSEB-MB Screen Display (3-phase 4-wire)
Display pattern
Screen set based on display pattern
No.1
No.2
No.3
No.4
No.5
No.6
No.7
No.8
No.9
No.10
P01
1
st
line
A
A
A
W
A
DA
2
nd
line
V
V
V
var
AN
DAN
3
rd
line
W
var
VA
PF
Hz
V
4
th
line
Wh
varh
VAh
Wh
Wh
Wh
P02
1
st
line
A1
DA1
V1N
W1
var1
VA1
PF1
A
A
DA
2
nd
line
A2
DA2
V2N
W2
var2
VA2
PF2
Hz
AN
DAN
3
rd
line
A3
DA3
V3N
W3
var3
VA3
PF3
W
var
VA
4
th
line
Aavg
DAavg
VLN
avg
W
∑
var
∑
VA
∑
PF
∑
Wh
varh
VAh
P00
1
st
line Free 1 Free 1 Free 1 Free 1
2
nd
line Free 1 Free 1 Free 1 Free 1
3
rd
line Free 1 Free 1 Free 1 Free 1
4
th
line Free 2 Free 2 Free 2 Free 2
Note 1. Selectable elements for “Free 1” include A, AN, DA, DAN, V, W var, VA, PF, and Hz. Selectable elements for “Free 2”include Wh, -Wh, varh, and VAh.
Display pattern
Additional screens (set in set-up menu Nos. 3 and 8)
No.11 No.12 No.13 No.14 No.15 No.16 No.17 No.18 No.19
No.20
No.21 No.22
Wh
Wh
(exported) varh
varh
imported
(Lead)
varh
exported
(Lag)
varh
exported
(Lead)
VAh Harmonic
current
Harmonic
current
Phase N
Harmonic
voltage
Operating
time 1
Operating
time 2
Common to
P00 to P02
1
st
line
–
–
–
–
–
–
–
1-phase
value
N-phase
value
1-phase
value
–
–
2
nd
line
Wh
Wh
exported varh
varh
imported
(Lead)
varh
exported
(Lag)
varh
exported
(Lead)
VAh
2-phase
value
–
2-phase
value
hour
1 hour 2
3
rd
line
3-phase
value
–
3-phase
value
–
–
4
th
line
Degree
number
Degree
number
Degree
number
Operating
time
Operating
time
Note 2. The additional screen is displayed when it is set to “ON
(Display)” in the setting menu.
Note 3. Wh in the table indicates Wh imported. The varh indicates varh imported (Lag).
Note 4. The additional screen for Wh, varh, and VAh of “P00” is not displayed unless Wh, varh, and VAh are set as the display elements.
»
ME96SSEB-MB Screen Display (3-phase 3-wire, 1-phase 3-wire, 1-phase 2-wire)
Display pattern
Screen set based on display pattern
No.1
No.2
No.3
No.4
No.5
No.6
P01
1
st
line
A
A
A
W
A
2
nd
line
V
V
V
var
DA
3
rd
line
W
var
VA
PF
Hz
4
th
line
Wh
varh
VAh
Wh
Wh
P02
1
st
line
A1
DA1
V12
W
A
A
2
nd
line
A2
DA2
V23
var
Hz
V
3
rd
line
A3
DA3
V31
PF
var
VA
4
th
line
Aavg
DAavg
Vavg
Wh
varh
VAh
P00
1
st
line Free 1 Free 1 Free 1 Free 1
2
nd
line Free 1 Free 1 Free 1 Free 1
3
rd
line Free 1 Free 1 Free 1 Free 1
4
th
line Free 2 Free 2 Free 2 Free 2
Note 1. In the case of 1-phase 2-wire setting, the display pattern P02 cannot be set.
Note 2. Selectable elements for Free 1 include A, DA, V, W, var, VA, PF, and Hz. Selectable elements for Free 2 include Wh, -Wh, varh, and VAh.
Display pattern
Additional screens (set in set-up menu Nos. 3 and 8)
No.7
No.8
No.9
No.10 No.11 No.12 No.13 No.14 No.15
No.16
No.17
Wh
Wh
(exported) varh
varh
imported
(Lead)
varh
exported
(Lag)
varh
exported
(Lead)
VAh Harmonic
current
Harmonic
voltage
Operating
time 1
Operating
time 2
Common to
P00 to P02
1
st
line
–
–
–
–
–
–
–
1-phase
value
1-phase
value
–
–
2
nd
line
Wh
Wh
exported varh
varh
imported
(Lead)
varh
exported
(Lag)
varh
exported
(Lead)
VAh
2-phase
value
3-phase
value
hour
1 hour 2
3
rd
line
3-phase
value
–
–
–
4
th
line
Degree
number
Degree
number
Operating
time
Operating
time
Note 3. The additional screen is displayed when it is set to “ON (Display)” in the setting menu.
Note 4. Wh in the table indicates Wh imported. The varh indicates varh imported (Lag).
Note 5. The additional screen for Wh, varh, and VAh of “P00” is not displayed unless Wh, varh, and VAh are set as the display elements.
Note 6: The 2-phase value of harmonic current (No.14) is displayed only for 3-phase 3-wire system (3CT).
»
Phase/Wire Displays
The phase/wire system will be displayed as shown in the following table and is common for all models.
Phase/Wire settings
Top phase display
1P2W
1P3W(1N2)
1P3W(1N3)
3P3W
current
1
None
1
1
1
2
None
N
N
2
3
None
2
3
3
Voltage
12
None
1N
1N
12
23
None
2N
3N
23
31
None
12
13
31
27
28
Summary of Contents for ME96 Series
Page 1: ...FACTORY AUTOMATION ELECTRONIC MULTI MEASURING INSTRUMENT ME96SS ...
Page 29: ...Memo 28 ...
Page 38: ... MEMO 37 ...
Page 39: ... MEMO 38 ...