Operating Instructions
Set-up menu 2: CC-Link Communication settings
(when ME-0040C-SS96 is installed)
* Only for ME96SSHB-MB or ME96SSRB-MB, it is applicable.
Set-up menu
DISPLAY SET
DISPLAY SET
q
Communication setting
selection
Adjust the set-up menu No. to “2”.
Set-up menu 2: MODBUS TCP Communication settings
(when ME-0000MT-SS96
*1
or ME-0040MT2-SS96
*2
is installed)
*1 Only for ME96SSHB-MB or ME96SSRB-MB, it is applicable.
*2 Only for ME96SSHB-MB, it is applicable.
DISPLAY SET
SET
Set-up menu
t
Reset communication
r
Set CC-Link
communication version
y
Reset communication
DISPLAY SET
DISPLAY SET
w
CC-Link communication
station number
e
CC-Link communication
baud rate
e
Set the CC-Link communication speed.
w
DISPLAY SET
Set-up menu
e
MODBUS RTU
communication parity
DISPLAY SET
r
MODBUS RTU
communication stop bit
e
Set the MODBUS RTU communication parity.
r
Set the MODBUS RTU communication stop bit.
Stop bit 1 Stop bit 2
Select another set-up menu or end set-up.
non
odd
even (EVEn)
<Continued from previous page>
DISPLAY SET
DISPLAY SET
DISPLAY SET
w
MODBUS TCP
communication IP address
r
Use/non-use of MODBUS
TCP communication default
gateway
DISPLAY SET
e
MODBUS TCP
communication subnet mask
DISPLAY SET
DISPLAY SET
SET
t
MODBUS TCP
communication default gateway
‡
To continue to set-up
Select the menu
No. using the or
button.
‡
To finish set-up
Press the or button
to display the End screen,
then press the
button to save settings.
SET
Select another set-up menu or end set-up.
‡
To continue to set-up
Select the menu
No. using the or
button.
‡
To finish set-up
Press the or button
to display the End screen,
then press the
button to save settings.
SET
When “MODBUS RTU communication” is selected, set the communication conditions
as stated in and after
q
MODBUS RTU communication address on page 16.
w
Set the CC-Link communication station number.
156 kbps
625 kbps
2.5 Mbps
5 Mbps
10 Mbps
r
Set the CC-Link communication version.
Version 1.10 Version 2.00
t
Set to “on” if changes have been made to the CC-Link settings.
(If not set to “on,” changes will not be effective.)
e
r
e
q
r
t
q
Select CC-Link or MODBUS RTU communication.
CC
: CC-Link communication
Mb. rtu : MODBUS RTU communication
Set-up menu
Adjust the set-up menu No. to “2”.
q
Communication setting
selection
When “MODBUS RTU communication” is selected, set the communication conditions
as stated in and after
q
MODBUS RTU communication address on page 16.
q
Select MODBUS TCP communication or MODBUS RTU communication.
Mb.tcp : MODBUS TCP communication
Mb.rtu : MODBUS RTU communication
w
Set the IP address of MODBUS TCP communication.
e
Set the sub-net mask of MODBUS TCP communication.
Select one of the sub-net masks shown in the following table.
(Non-use)
(Use)
Allowable IP addresses:
000.000.000.000 - 192.168.3.10 - 255.255.255.255
r
Determine whether or not to use the default gateway of MODBUS TCP communication.
t
Set the default gateway of MODBUS TCP communication.
When the default gateway is not used, this window is not displayed.
Allowable default gateways:
000.000.000.000 - 127.0.0.1 - 255.255.255.255
y
If settings relating to MODBUS TCP communication have been changed,
turn on this item.
(If it is not turned on, the changes will not be enabled.)
oFF on
oFF on
Set-up menu
Select another set-up menu or end set-up.
‡
To continue to set-up
Select the menu
No. using the or
button.
‡
To finish set-up
Press the or button
to display the End screen,
then press the
button to save settings.
SET
oFF on
Possible station number settings: 1-64
w
e
q
r
t
y
(1)
128.0.0.0
(9)
255.128.0.0
(17)
255.255.128.0
(25)
255.255.255.128
(2)
192.0.0.0
(10)
255.192.0.0
(18)
255.255.192.0
(26)
255.255.255.192
(3)
224.0.0.0
(11)
255.224.0.0
(19)
255.255.224.0
(27)
255.255.255.224
(4)
240.0.0.0
(12)
255.240.0.0
(20)
255.255.240.0
(28)
255.255.255.240
(5)
248.0.0.0
(13)
255.248.0.0
(21)
255.255.248.0
(29)
255.255.255.248
(6)
252.0.0.0
(14)
255.252.0.0
(22)
255.255.252.0
(30)
255.255.255.252
(7)
254.0.0.0
(15)
255.254.0.0
(23)
255.255.254.0
(8)
255.0.0.0
(16)
255.255.0.0
(24)
255.255.255.0
17
18