Operating Instructions
Set-up menu 3: Display settings (active energy, harmonics measurement, etc.)
DISPLAY SET
Set-up menu
SET
Set-up menu
w
Harmonic display
w
DISPLAY SET
e
Unbalance rate display
DISPLAY SET
<Example display screens>
Combination I
: Imported
: Exported
: varh (lead)
: varh (lag)
Combination II
Combination III
Combination IV
q
Active/Reactive energy
measurement method
Set-up menu 6: Built-in logging settings
* Only for ME96SSHB-MB, ME96SSRB-MB, it is applicable.
Adjust the set-up menu No. to “3”.
q
Set the display combination for imported/exported and lag/lead of active/reactive energy and
the measurement method for reactive energy.
Combinations I, II =>
Suitable for measurement in facilities not equipped with in-house generators,
and measuring reactive power of capacitor load, where power factor is around zero generally.
Combinations III, IV => Suitable for measurements in facilities equipped with in-house generators.
Imported Exported
Lag
Lead
Lag
Lead
Reactive energy
measurement
method
2 Quadrants Measurement
4 Quadrants Measurement
Combinations
(set value)
I
II
III
IV
Display combinations
Wh
varh
Imported
Exported
w
Set whether to display the harmonic measured value.
on oFF
(Display)
(Not display)
When you set to “on (Display)”, harmonic measured values are displayed on
the additional screen of display pattern.
Select another set-up menu or end set-up
Adjust the set-up menu No. to “6”. (See the drawing on the right)
Clears logging data stored in the main body
‡
To continue to set-up
Select the menu
No. using the or button.
‡
To finish set-up
Press the or button
to display the End screen,
then press the button
to save settings.
SET
DISPLAY SET
DISPLAY SET
Set-up menu
no
yES
(Not clear)
(Clear)
When yES (Clear) is selected above, the confirmation screen appears to ask whether or not to clear data.
DISPLAY SET
DISPLAY SET
Sets whether or not to use the built-in logging function.
Sets a logging item pattern to choose data that are internally logged.
Patterns usable for setting:
By selecting LP00, you can freely choose logging items.
Logging item patterns for LP01 & LP02 are defined as in the table below.
Detailed data are recorded in an interval that is shorter than that of 1-hour data.
Logging cycle of the detailed data is set in [
t
Built-in logging period].
on
LP00 LP01 LP02
oFF
(Use)
(Non-use)
Logging item pattern
LP01
LP02
Data 1 (integrated value)
Data 2 (integrated value)
Data 3 (integrated value)
Data 4 (integrated value)
Data 5 (integrated value)
Data 1
Data 2
Data 3
Data 4
Data 5
Data 6
Data 7
Data 8
Data 9
Data 10
Data 11
Data 12
Data 13
Data 14
Data 15
Wh imported
Wh exported
varh imported (LAG)
varh imported (LEAD)
VAh
W (total) present value
PF (total) present value
Hz (present value)
var (total) present value
VA (total) present value
A (avg) present value
V (line voltage) (avg) present value
DW (last value)
Dvar (last value)
DVA (last value)
DW (peak value)
Dvar (peak value)
DVA (peak value)
A1 Harmonic present value (total)
V1N Harmonic voltage phase voltage distortion ratio (total)
Wh imported
Wh exported
varh imported (LAG)
varh imported (LEAD)
VAh
W (total) present value
PF (total) present value
Hz (present value)
A (avg) present value
V (line voltage) (avg) present value
A1 present value
A2 present value
A3 present value
AN present value
V12 present value
V23 present value
V31 present value
V1N present value
V2N present value
V3N present value
Phase wiring type setting: 3-phase 4-wire system
Logging item pattern
LP01
LP02
Data 1 (integrated value)
Data 2 (integrated value)
Data 3 (integrated value)
Data 4 (integrated value)
Data 5 (integrated value)
Data 1
Data 2
Data 3
Data 4
Data 5
Data 6
Data 7
Data 8
Data 9
Data 10
Data 11
Data 12
Data 13
Data 14
Data 15
Wh imported
Wh exported
varh imported (LAG)
varh imported (LEAD)
VAh
W (total) present value
PF (total) present value
Hz (present value)
var (total) present value
VA (total) present value
A (avg) present value
V (line voltage) (avg) present value
DW (last value)
Dvar (last value)
DVA (last value)
DW (peak value)
Dvar (peak value)
DVA (peak value)
A1 Harmonic present value (total)
V12 Harmonic voltage phase voltage distortion ratio (total)
Wh imported
Wh exported
varh imported (LAG)
varh imported (LEAD)
VAh
W (total) present value
PF (total) present value
Hz (present value)
A (avg) present value
V (line voltage) (avg) present value
A1 present value
A2 present value
A3 present value
—
V12 present value
V23 present value
V31 present value
—
—
—
Setting of phase wiring system: 3-phase 3-wire_2CT, 3-phase 3-wire_3CT, 1-phase 3-wire system
Logging item pattern
LP01
LP02
Data 1 (integrated value)
Data 2 (integrated value)
Data 3 (integrated value)
Data 4 (integrated value)
Data 5 (integrated value)
Data 1
Data 2
Data 3
Data 4
Data 5
Data 6
Data 7
Data 8
Data 9
Data 10
Data 11
Data 12
Data 13
Data 14
Data 15
Wh imported
Wh exported
varh imported (LAG)
varh imported (LEAD)
VAh
W (total) present value
PF (total) present value
Hz (present value)
var (total) present value
VA (total) present value
A (avg) present value
V (line voltage) (avg) present value
DW (last value)
Dvar (last value)
DVA (last value)
DW (peak value)
Dvar (peak value)
DVA (peak value)
A1 Harmonic present value (total)
V12 Harmonic voltage phase voltage distortion ratio (total)
Wh imported
Wh exported
varh imported (LAG)
varh imported (LEAD)
VAh
W (total) present value
PF (total) present value
Hz (present value)
A (avg) present value
V (line voltage) (avg) present value
A1 present value
—
—
—
V12 present value
—
—
—
—
—
Setting of phase wiring system: 1-phase 2-wire system
w
Built-in logging
Data clear
no
yES
(Not clear)
(Clear)
e
Built-in logging
Use/non-use
r
Built-in logging
item patterns
q
Optional selection
DISPLAY SET
Select analog output, built-in logging, or optional logging.
Ao PLUG buiLt
(Analog output) (Optional logging) (Built-in logging)
The explanation here is about built-in logging settings.
For the analog output settings, refer to Set-up menu 6: Analog output setting.
For the optional logging settings, refer to Set-up menu 6: Logging setting.
Note. When ME-4210-SS96B or ME-0000BU-SS96 of optional module is not installed, this setting is skipped.
e
e
Set whether to display unbalance rate.
on oFF
(Display)
(Not display)
When you set to “on (Display)”, voltage/current unbalance rate
can be displayed on the additional screen of display pattern.
Note. For 1-phase 2-wire system, this setting is skipped.
19
20