*1 : ME-0040MT2-SS96 is only applicable to ME96SSHB-MB with firmware
version 01.01 or later.
CC-Link System (With optional plug-in module (ME-0040C-SS96))
MODBUS TCP System (With optional plug-in module (ME-0000MT-SS96/ME-0040MT2-SS96 *
1
))
Data Logging (Built-in logging function and optional plug-in module (ME-0000BU-SS96))
Analog/Pulse/Alarm Output System (With optional plug-in module (ME-4210-SS96B))
»
Applicable to analog output, pulse output and alarm output with the aid of the optional module
ME-4210-SS96B.
»
Remote monitoring of A, DA, V, W, var, VA, PF, Hz, Harmonics Current RMS value and
Harmonics voltage RMS value at 4 mA to 20 mA output (max. 4 outputs).
»
Active energy, reactive energy, apparent power and periodic energy can be monitored by
pulse output (max. 2 pulses).
»
Can remotely monitor upper/lower limit alarm by digital output (max. 2 points).
»
This is a MODBUS TCP communication unit that can be used in the Ethernet system. The number of
network system selection methods is increased, and Ethernet and MODBUS RTU communication can
be duplicated.
»
The optional plug-in module ME-0040MT2-SS96 has 2 Ethernet ports, so straight-line topology is
possible without using Ethernet SWITCH/HUB.
»
The optional plug-in module ME-0040MT2-SS96 has 4 digital inputs, so remote monitoring of status
signals is possible without a PLC.
»
Digital input signal can be latched for over 30
ms,
and there is no need for external latch circuits.
»
The ME96SSHB-MB/ME96SSRB-MB has a built-in logging function stores measurement data as logging data in the internal non-volatile
memory. The data to be stored as events occurred in this instrument are alarm data, the recorded time of the Max/Min value, and system log
data. The stored data can be read from MODBUS RTU communication.
»
Optional module ME-0000BU-SS96 can memorize the data of various quantities related to electricity measured by ME96SS-Ver.B for a certain
period. Therefore, measurement data can be backup even when the MODBUS RTU communication of ME96SS-Ver.B fails.
Memorized measurement data can be output to an SD memory card in CSV format. You can check the data files output to the SD memory
card by Microsoft Excel.
<Analog output specifications>
• 4 mA to 20 mA
• 4 outputs
• Resistance load 600
Ω
or less
<Pulse output specifications>
• No-voltage a contact point
• 35 V DC, 0.1 A
• Select output from pulse widths of 0.125 s, 0.5 s or 1 s
<MODBUS TCP Communication Specifications>
• Ethernet port : 10BASE-T/100BASE-TX
• Maximum segment length : 100 m
<Optional Plug-in Module ME-0000MT-SS96>
• Number of ports : 1
• Digital Input : non
<Optional Plug-in Module ME-0040MT2-SS96 *
1
>
• Number of ports : 2
• Digital Input : 4 points (24 V DC)
<Alarm output specifications>
• No-voltage a contact point
• 35 V DC, 0.1 A
<Digital input specifications>
• 1 point (24 V DC)
Outline and Features
ME96 Super-S Series Ver.B Features
ME96SSHB-MB
(High-performance model)
ME96SSRB-MB
(Standard model)
ME96SSEB-MB
(Economy model)
MODBUS RTU communication
Plug-in module (options)
• Analog/Pulse/Digital output/input
• CC-Link communication
• Digital input/output (for MODBUS RTU communication)
• Backup (on SD card)
• MODBUS TCP communication
MODBUS RTU communication
Plug-in module (options)
• Analog/Pulse/Digital output/input
• CC-Link communication
• Digital input/output (for MODBUS RTU communication)
• Backup (on SD card)
• MODBUS TCP communication
MODBUS RTU communication
A, DA, V, Hz = ±0.1%
W, var, VA, PF = ±0.2%
VAh = ±2.0%
Wh = class 0.5S (IEC62053-22)
varh = class 1S (IEC62053-24)
Harmonics = 31
st
-deg (max)
Rolling demand = W, var, VA
A, DA, V = ±0.2%
Hz = ±0.1%
W, var, VA, PF = ±0.5%
VAh = ±2.0%
Wh = class 0.5S (IEC62053-22)
varh = class 1S (IEC62053-24)
Harmonics = 19
th
-deg (max)
Rolling demand = W, var, VA
A, DA, V = ±0.5%
Hz = ±0.2%
W, var, VA, PF = ±0.5%
VAh = ±2.0%
Wh = class 0.5S (IEC62053-22)
varh = class 1S (IEC62053-24)
Harmonics = Only total
Optional Plug-in Modules
Note 1: Optional Plug-in Module can not be used with ME96SSEB-MB.
Note 2: For details of each characteristic, refer to the specifications section.
*1: 2 ports for daisy chain, one IP address.
*2: Applicable only to firmware version 01.01 or later.
»
Optimum transmission system for remote monitoring using Mitsubishi PLC.
»
Contact signals can be remotely monitored by installing the optional module ME-0040C-SS96. This is
helpful in wiring and space saving.
»
Digital input signals can be latched for over 30 ms, and there is no need for external latch circuits.
Abnormal Signal (Facility)
Abnormal Signal (Earth Leakage)
Abnormal Signal (Temperature)
Circuit Breaker Status Signal, etc.
Abnormal Signal (Facility)
Abnormal Signal (Earth Leakage)
Abnormal Signal (Temperature)
Circuit Breaker Status Signal, etc.
<CC-Link Interface>
• Max. Baud rate: 10 Mbps
• Max. Connection Distance: 100 m (10 Mbps)-
1,200 m (156 kbps)
• Max. Connection Units: 42
• Digital Input: 4 points (24 V DC)
CC-Link
Ethernet
MELSEC Series
MODBUS RTU System
Central monitor
RS485/USB
converter
RS485 (MODBUS RTU)
USB
»
MODBUS RTU communication system optimizes computer monitoring operations.
»
In addition, when ME-0052-SS96 is installed, remote monitoring of digital input signals and on/off
control of digital output signals are possible. Therefore, no other DI/DO terminals are required.
»
Digital input signals can be latched for over 30 ms, and there is no need for external latch circuits.
ME-0052-SS96
optional unit
Tripping
Closing
AL
PAL
TAL
Turning on/off breaker, etc.
<MODBUS RTU Interface Specifications>
• Max. Baud rate: 38.4 kbps
• Max. Connection Distance: 1,200 m
• Max. Connection Units: 31
<Optional Plug-in Module ME-0052-SS96>
• Digital Input: 5 points (24 V DC)
• Digital Output: 2 points (35 V DC)
Model name
Transmission/Option specifications
Main measurement items
»
Added measurement function, reactive energy, apparent energy, reactive power and apparent power for ME96SSEB-MB.
»
Realized downsizing for ME96SSEB-MB.
Improved Measurement Functions
It contributes to
space saving!
ME96SSEA-MB
(Conventional type)
ME96SSEB-MB
(New type)
36.0 mm
13.0 mm
Compact size
Central monitor
For ME96SSHB-MB with ME-0040MT2-SS96
Ethernet
90.2
mm
(110.9 mm)
20.7 mm
Model name
Characteristics
Analog output
Pulse/Alarm output
Digital input
Digital output
Communication
Logging function
Used with
ME-4210-SS96B
4
2
1
ME96SSHB-MB
ME96SSRB-MB
ME-0040C-SS96
4
CC-Link
ME-0052-SS96
5
2
ME-0000BU-SS96
6 items
ME-0000MT-SS96
MODBUS TCP 1 port
ME-0040MT2-SS96
4
MODBUS TCP 2 ports *
1
ME96SSHB-MB *
2
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Ethernet
Analog output
Pulse output
Alarm output
3