Specifications
‡
Standards Compliance
Electromagnetic Compatibility
Emissions
Radiated Emission
EN 61326-1 / EN 55011, CISPR 11
FCC Part15 Subpart B Class A
Conducted Emission
EN 61326-1 / EN 55011, CISPR 11
FCC Part15 Subpart B Class A
Harmonics Measurement
EN 61000-3-2
Flicker Meter Measurement
EN 61000-3-3
Immunity
Electrostatic discharge Immunity
EN 61326-1, EN IEC 61000-6-2 / EN 61000-4-2
Radio Frequency Electromagnetic field Immunity
EN 61326-1, EN IEC 61000-6-2 / EN 61000-4-3
Electrical Fast Transient/Burst Immunity
EN 61326-1, EN IEC 61000-6-2 / EN 61000-4-4
Surge Immunity
EN 61326-1, EN IEC 61000-6-2 / EN 61000-4-5
Conducted Disturbances, Induced By Radio Frequency Fields Immunity
EN 61326-1, EN IEC 61000-6-2 / EN 61000-4-6
Power Frequency Magnetic Field Immunity
EN 61326-1, EN IEC 61000-6-2 / EN 61000-4-8
Voltage Dips and Short Interruptions
EN 61326-1, EN IEC 61000-6-2 / EN 61000-4-11
Safety
Europe
CE, as per EN 61010-1: 2010 (3
rd
Edition)
U.S. and Canada
UL Recognized Component as per UL 61010-1, IEC 61010-1
Installation Category
III
Measuring Category
III
Pollution Degree
2
‡
MODBUS RTU Communication Specifications
Item
Specification
Interface
RS-485 2-wire half-duplex transmission
Protocol
RTU (binary data transfer)
Transmission method
Asynchronous
Connection type
Multi-point bus
Baud rate
2400, 4800, 9600, 19200, 38400 bps
Data bit
8
Stop bit
1, 2
Parity
ODD, EVEN, NONE
Address
1 to 255 (0: for broadcast mode)
Distance
1,200 m (max)
Max. connectable units
31 units
Terminal Resistance
120
Ω
1/2 W
Recommended Cable
Shielded twisted-pair AWG 24 to 14
For more information on data, please refer to the following document.
· Electronic Multi-Measuring Instrument ME series MODBUS Interface specifications…LSPM-0075
‡
CC-Link Communication Specifications for optional plug-in module
Item
Specification
No. of occupied stations
1 Station Remote device station
CC-Link version
CC-Link Ver 1.10 / Ver 2.00
Baud rate
10 Mbps / 5 Mbps / 2.5 Mbps / 625 kbps / 156 kbps
Transmission method
Broadcast polling system
Synchronous method
Frame synchronous system
Encoding method
NRZI
Transmission path format
Bus format (EIA RS485)
Transmission format
HDLC
Error control system
CRC (X
16
+ X
12
+ X
5
+ 1)
Number of connectable units
42 units (max, remote device station)
Remote station numbers (station numbers)
1 to 64
For CC-Link connection cables, please use the dedicated cables.
For information regarding dedicated cables, please refer to the CC-Link Partner Product Catalog published by the CC-Link Partner Association or CC-Link Partner Product
Information on the CC-Link Partner Association website (http://www.cc-link.org).
Notes 1. Dedicated CC-Link cables compatible with Ver. 1.00 cannot be used in tandem with dedicated CC-Link high-performance cables compatible with Ver. 1.00.
Notes 2. In the case of systems consisting of units compatible with Ver. 1.00, 1.10 or 2.00 used in tandem with Ver. 1.00 or 1.10 cables, Ver. 1.00 specifications will
apply for the maximum total cable length and length of cables between stations.
Notes 3. For terminal resistance, be sure to use 110
Ω
±5% (1/2 W product) when using dedicated CC-Link cables or 130
Ω
±5% (1/2 W product) when using dedicated
CC-Link high-performance cables.
For more information on data, please refer to the following document.
· Electronic Multi-Measuring Instrument programming manual (CC-Link)……………………………………………LEN080334
· Electronic Multi-Measuring Instrument programming manual (CC-Link)(For ver. 2 remote device station)…LEN130391
‡
Input/Output Specifications for optional plug-in module
Item
Specifications
Optional Plug-in Module type
Analog output
Output specifications
4 mA to 20 mA
ME-4210-SS96B
Load resistance
600
Ω
or less
Response time
1 second or less
(Hz: 2 seconds or less, HI, HV: 5 seconds or less)
Pulse/Alarm output
Switch type
No-voltage a-contact
ME-4210-SS96B
Contact capacity
35 V DC, 0.1 A or less
Pulse width
0.125 s, 0.5 s, 1.0 s
Digital input (DI)
Contact capacity
24 V DC (19 V DC to 30 V DC), 7 mA or less
ME-4210-SS96B, ME-0040C-SS96,
ME-0052-SS96, ME-0040MT2-SS96B
Signal width
30 ms or more
Digital output (DO)
Switch type
No-voltage a-contact
ME-0052-SS96
Contact capacity
35 V DC, 0.2 A or less
11
12
Summary of Contents for ME96 Series
Page 1: ...FACTORY AUTOMATION ELECTRONIC MULTI MEASURING INSTRUMENT ME96SS ...
Page 29: ...Memo 28 ...
Page 38: ... MEMO 37 ...
Page 39: ... MEMO 38 ...