Specifications
Model name
ME96SSRB-MB
Phase wire system
3-phase 4-wire, 3-phase 3-wire (3CT, 2CT), 1-phase 3-wire, 1-phase 2-wire (common use)
Rating
Current
5 A AC, 1 A AC (common use)
Voltage
3-phase 4-wire: max 277/480 V AC
3-phase 3-wire: (DELTA) max 220 V AC, (STAR) max 440 V AC
1-phase 3-wire: max 220/440 V AC
1-phase 2-wire: (DELTA) max 220 V AC, (STAR) max 440 V AC
Frequency
50/60 Hz (common use)
Item
Measurement items
Class
Measuring
element
Current (A)
A1, A2, A3, AN, A
AVG
±0.2%
Current demand (DA)
DA1, DA2, DA3, DAN, DA
AVG
Voltage (V)
V12, V23, V31, V
AVG
(L-L), V1N, V2N, V3N, V
AVG
(L-N)
Active power (W)
W1, W2, W3,
∑
W
±0.5%
Reactive power (var)
var1, var2,var3,
∑
var
Apparent power (VA)
VA1, VA2, VA3,
∑
VA
Power factor (PF)
PF1, PF2, PF3,
∑
PF
Frequency (Hz)
Hz
±0.1%
Active energy (Wh)
Imported, Exported
Class 0.5S (IEC62053-22)
Reactive energy (varh)
Imported lag, Imported lead, Exported lag, Exported lead
Class 1S (IEC62053-24)
Apparent energy (VAh)
Im Exported
±2.0%
Harmonic current (HI)
Total, 1
st
to 19
st
(Odd degree only)
±1.0%
Harmonic voltage (HV)
Total, 1
st
to 19
st
(Odd degree only)
Rolling demand active power (DW)
Rolling block, Fixing block (Select either of them according to the settings.) ±0.5%
Rolling demand reactive power (Dvar)
Rolling block, Fixing block (Select either of them according to the settings.)
±1.0%
Rolling demand apparent power (DVA)
Rolling block, Fixing block (Select either of them according to the settings.)
Periodic active energy (Wh)
Periodic active energy 1, Periodic active energy 2, Periodic active energy 3 Class 0.5S
Operating time (h)
Operating time 1, Operating time 2
(Reference)
Current unbalance rate (Aunb)
Aunb
(Reference)
Voltage unbalance rate (Vunb)
Vunb
(Reference)
CO
2
equivalent
kg
(Reference)
Item
Specifications
Measuring
Method
Instantaneous Value
A, V: RMS value calculation; W, var, VA, Wh, varh, VAh: Digital multiplication;
PF: Power ratio calculation; Hz: Zero-cross; HI, HV: FFT
Demand Value
DA: Thermal type calculation, DW, Dvar, DVA: Rolling demand calculation
Display
Display type
LCD with LED backlight
Number of display digits or
segments
Digital section
First to third line indication: 4 digits, Fourth line indication: 6 digits
A, DA, V, W, var, VA, PF, DW, Dvar, DVA: 4 digits; Hz: 3 digits;
Wh, varh, VAh: 9 digits (6-digit or 12-digit is also available.);
Harmonic distortion ratio/content rate: 4 digits; Harmonic RMS value: 4 digits;
Operating time: 6 digits; Digital input/output: I/O
Display update time interval
0.5 s, 1 s (selectable)
Communication
MODBUS RTU communication
Built-in
logging
Logging mode
Automatic overwrite update
Logging data type
Measuring data
*1
Measuring data and time data are logged at the interval set at the data logging period. (15 min, 30 min,
60 min)
Alarm log
Time data at alarm generating/cancellation and at waiting for alarm cancellation
The recorded time of the
Max/Min value
Max/Min value data and time data
Number of logging items
Measuring data
Integrated value data: 5 items, Data other than integrated value: 15 items, Total: A maximum of 20 items
Alarm log
The number of the set alarms
The recorded time of the
Max/Min value
The total is 19 items: Current Max/Min (AVG), Line voltage Max/Min (AVG), Phase voltage Max/Min
(AVG), Total active power Max/Min (AVG), Total power factor Max/Min (AVG), Frequency Max/Min (AVG),
Total reactive power Max/Min, Total apparent power Max/Min, Total harmonic current RMS Max value,
Harmonic line voltage distortion ratio Max total, Harmonic phase voltage distortion ratio Max total
Internal memory logging period
Measuring data
30 days (Logging period: 15 minutes), 60 days (Logging period: 30 minutes), 120 days (Logging period:
60 minutes),
Alarm log
100 records
The recorded time of the
Max/Min value
1 record for every Max/Min value factor
System log data
100 records
Saving logging data
Use of nonvolatile memory
How to acquire logging data
Acquire the logging data via MODBUS
®
RTU Communication
Clock accuracy
± 1 minute per month, typical
Connectable Optional Plug-in Module
ME-4210-SS96B, ME-0040C-SS96, ME-0052-SS96, ME-0000MT-SS96, ME-0000BU-SS96
Power interruption backup
Use of nonvolatile memory (Items: settings, MAX/MIN value, active energy, reactive energy, apparent
energy, periodic active energy, rolling demand, operating time)
Built-in logging
Use of nonvolatile memory (Logging data, System log data)
VA Consumption
Voltage circuit
Each phase: 0.1 VA (at 110 V AC), 0.2 VA (at 220 V AC), 0.4 VA (at 440 V AC)
Current circuit
Each phase: 0.1 VA
Auxiliary power circuit
13 VA (at 110 V AC), 14 VA (at 220 V AC), 9 W (at 100 V DC)
Auxiliary power
100 V to 240 V AC (±15%), 100 V to 240 V DC (-30% +15%)
Weight
0.5 kg
Dimensions
96 (H) × 96 (W) × 90 (D) mm
Mounting method
Embedded
Operating temperature/humidity
-5°C to +55°C (Daily average temperature: 35°C or less), 0% to 85% RH, Non condensing
Storage temperature/ humidity
-25°C to +75°C (Daily average temperature: 35°C or less), 0% to 85% RH, Non condensing
Note 1. The class value represents the ratio to the rated value (100%).
Note 2. For measurement where the harmonic distortion ratio (content rate) is 100% or more, the class can exceed ±1.0%.
Note 3. Harmonic current cannot be measured without voltage input.
Note 4. Using the conventional ME-4210-SS96 (Optional Plug-in Module), the CE marking and UL standards safety certification requirements cannot be met.
*1: Integrated values (Wh, varh, and VAh) are measured values of ME96SS. They are not differential values by logging period.
‡
ME96SSRB-MB
9
10
Summary of Contents for ME96 Series