Safety Precautions
To ensure safety, read the following items carefully before use and always comply with procedures during use. Special attention should be given to
items enclosed in a box and marked “Caution.” Additionally, please carefully read the operations manual supplied with the product before use, and
ensure that the manual read by the end user as well.
3
Connections
See pages 30-32 of this catalog for information regarding connections.
4
Preparations Before Use
• Before use, perform settings such as the VT primary voltage, CT primary current, power scale and demand time limit in accordance with the operations manual
supplied with the product; setting errors may cause incorrect measurement/operation.
5
Usage Procedures
• Use the products within the rated range. Using the products outside the rated range may cause erroneous operation or product malfunction.
• Do not use the products for special applications such as nuclear power, aerospace or medical devices/systems.
100 V AC to 240 V AC (±15%) 50 Hz to 60 Hz
100 V DC to 240 V DC (-30%, +15%)
3-phase 4-wire: max 277/480 V AC
3-phase 3-wire: (DELTA) max 220 V AC
(STAR) max 440 V AC
1-phase 3-wire: max 220/440 V AC
1-phase 2-wire: (DELTA) max 220 V AC
(STAR) max 440 V AC
Category
Ⅲ
P1, P2, P3, PN terminals
MA, MB terminal
+C1, C1, +C2, C2, +C3, C3 terminals
Category
Ⅲ
5 A (CT secondary side), max 30 V AC
Auxiliary power supply
Measuring element
Current
Voltage
50 Hz or 60 Hz
Frequency
■
Auxiliary power supply and measuring elements
max 35 V DC
MODBUS RTU communication
MODBUS TCP communication
CC-Link communication
Digital input
Digital output
Analog output
Pulse/Alarm output
T/R+, T/R-, SG terminals
Ethernet terminal
DA, DB, DG terminals
DI1, DI2, DI3, DI4, DI COM, DI+, DI-, DI1+, DI1-, DI2+, DI2-, DI3+, DI3-,
DI4+, DI4-, DI5+, DI5- terminals
DO1+, DO1-, DO2+, DO2- terminals
CH1+, CH1-, CH2+, CH2-, CH3+, CH3-, CH4+, CH4- terminals
C1A/A1, C1B/COM1, C2A/A2, C2B/COM2 terminals
■
Others
1
Usage Environment and Conditions
Do not use these products under any of the following conditions. Doing so may cause erroneous operation and/or reduced service life.
• Ambient temperature is outside the range of -5°C to +55°C • Daily average temperature over 35°C • Relative humidity over 85% RH non-condensing
• Presence of excessive dust, corrosive gas, salt or oil/smoke • Product is subject to excessive vibration or shock • Product is in direct contact with rain, water drops or
sunlight • Altitude is above 2,000 m • Excessive external noise • Pollution level is 2 or higher • Transient overvoltage is 4,000
V or higher • Presence of metal
fragments or conducting substances
2
Installation
Please note the following items regarding installation. To ensure safety, installation is to be performed by a qualified technical electrician.
• Affix the main unit to the panel before use • The LCD display contrast changes depending on the angle from which it is viewed. Install it in a position that ensures a
suitable angle of view. • Tighten screws using a torque of approx. 0.3-0.5 N·m • To prevent damage to the LCD, take care not to subject the LCD/front of the main unit to
shock/impact.
6
Repairing at Time of Malfunction/Error
• If a product listed in this catalog malfunctions, read the troubleshooting section of the operations manual (detailed version) and confirm the symptoms. If the problem
is not listed, please contact a Mitsubishi Electric representative.
7
Maintenance/Inspections
• Wipe away any dust/dirt on the surface of the product with a soft cloth.
• Do not leave chemical cloths, etc. in contact with the product for long periods, and avoid the use of benzene, thinner, etc. when wiping the product surface. Doing so
may cause deformation or cause the coating to peel away.
• To ensure correct use for the full service life of the product, please perform the following inspections:
q
Check for damage to the product
w
Check for display malfunctions (e.g., does not respond to input)
e
Check for loose installation or terminal block wire connections
(check regularly once every six months/year) always making sure that power has been turned off beforehand)
r
Check for unusual smell, noise or rise in temperature.
8
Storage
Do not store the product for long periods of time under any of the following conditions. Doing so may lead to a malfunction or reduced service life.
• Ambient temperature outside the range of -25°C to +75°C • Daily average temperature of more than 35°C • Relative humidity exceeding 85% RH or
condensation present • Excessive dust, corrosive gas, salt or oil/smoke present • Product is subject to excessive vibration or shock • Product is in
direct contact with rain, water drops or sunlight
9
Disposal
• These products do not use nickel-cadmium batteries. Dispose of them as industrial waste.
• The optional module ME-0000BU-SS96 contains a lithium battery. Dispose of the battery in accordance with the municipal regulations.
• In EU member states, there is a separate collection system for used batteries. Dispose of the batteries properly at the local collection/recycling center. The following
symbol is printed on the package of ME-0000BU-SS96.
This symbol is applicable only in EU member states. The symbol is designated in Article 20 “Information for end-users” and Annex II of the new European
Directive on batteries (2006/66/EC).
The above symbol indicates that the batteries must be disposed of after separation from general waste.
10
Warranty Period
The warranty period for the products in this catalog expires one year from the date of purchase or one year and six months after the date of
manufacture; whichever is earliest. Even during the warranty period, the warranty shall not apply to malfunctions attributable to intentional
negligence or erroneous use by the customer, and the fee for any repair required as the result of such negligence shall be the liability of the
customer.
Mitsubishi Electric shall not be liable for: Damage that cannot be attributed to Mitsubishi Electric; lost opportunity or earnings resulting from
failure of a Mitsubishi Electric product; damage, secondary damage or compensation for an accident resulting from special circumstances
regardless of whether or not the circumstances were foreseeable; or damage to products or other services for products not manufactured by
Mitsubishi Electric.
11
Product Exchange Cycle
Although it depends on usage conditions, as a guide, it is recommended that the products listed in this catalog be renewed after 10 years.
»
Trademarks
• MODBUS is a trademark of Schneider Electric USA Inc.
• Ethernet is a trademark of Fuji Xerox Co., Ltd.
• Microsoft, Excel is the registered trademark of the U.S. Microsoft Corporation in the U.S. and other countries.
• Other company and product names herein are trademarks or registered trademarks of their respective owners.
• In the text, trademark symbols such as "TM" and "®" may not be written.
• Do not make any modifications to the products. Using products after modification may cause a malfunction, electrical shock or fire.
CAUTION
• To ensure safety, connections are to be performed by an electrical engineer qualified in wiring.
• Check connection diagrams carefully before performing connections.
Incorrect connections may result in VT burnout caused by a VT secondary-side short circuit or high voltage on the CT
secondary side, which may lead to device malfunction, fire or electrical shock.
• Do not work with live wires; there is a risk of electric shock and exposure to high voltage due to short-circuiting or CT
secondary side opening, which may lead to malfunction, fire or electrical shock.
• Use electrical wire sizes compatible with the rated current. Use of unsuitable sizes may cause heat generation, which may lead
to a fire.
• After performing connections, check that no connections have been missed.
Missed connections may result in erroneous operation or high voltage on the CT secondary side, which may lead to a fire or
electrical shock.
• At the time of wiring, an electric wire can be broken by pulling with strong power.
(The load of pulling is less than 3-9 N)
CAUTION
• The optional module ME-0000BU-SS96 contains a lithium battery. Therefore, if it is thrown into the fire, it may generate heat,
rupture or ignite. Dispose of the lithium battery in accordance with the municipal regulations.
CAUTION
35
36
Summary of Contents for ME96 Series
Page 1: ...FACTORY AUTOMATION ELECTRONIC MULTI MEASURING INSTRUMENT ME96SS ...
Page 29: ...Memo 28 ...