63
7
7.2.3
Instruction codes
Instruction code definition
Set the instruction code using a remote register (RWw) (refer to
The definition read by the instruction code is stored in the remote register (RWr) (refer to
Item
Read/
write
Code
number
Description
Operation mode
Read
H7B
H0000: Network operation mode
H0001: External operation mode, External JOG operation mode
H0002: PU operation mode, External/PU combined operation modes 1 and 2,
PUJOG operation mode
Write
HFB
H0000: Network operation mode
H0001: External operation mode
H0002: PU operation mode (
Pr.79
= "6",
Pr.340
= "10 or 12")
Monitor
Output
frequency
Read
H6F
H0000 to HFFFF:
Running frequency: 0.01 Hz increments
Speed (machine speed): 1 increments
Output current
Read
H70
H0000 to HFFFF:
Output current (hexadecimal): Increments 0.01 A/0.1 A
Output voltage
Read
H71
H0000 to HFFFF:
Output voltage (hexadecimal): Increments 0.1 V
Special monitor
Read
H72
H0000 to HFFFF: Check the data of the monitor selected by the instruction code HF3.
Special monitor
selection No.
Read
H73
H01 to HFF: Selection of the monitored item (monitor code) (Refer to
If a monitor code out of the range is set, a range error occurs.
Write
HF3