26
INVERTER SETTING
Pr.340
setting
Pr.79
setting
Operation mode at power ON or power
restoration
Operation mode switchover
0
(initial
value)
0 (initial
value)
External operation mode
Switching among the External, PU, and NET operation
mode is enabled.
1
PU operation mode
PU operation mode fixed
2
External operation mode
Switching between the External and Net operation mode is
enabled.
Switching to the PU operation mode is disallowed.
3, 4
External/PU combined operation mode
Operation mode switching is disallowed.
6
External operation mode
Switching among the External, PU, and NET operation
mode is enabled while running.
7
X12 (MRS) signal ON: external operation mode
Switching among the External, PU, and NET operation
mode is enabled.
X12 (MRS) signal OFF: external operation mode
External operation mode fixed (Forcibly switched to
External operation mode.)
1, 2
0
NET operation mode
Same as when
Pr.340
= "0"
1
PU operation mode
2
NET operation mode
3, 4
External/PU combined operation mode
6
NET operation mode
7
X12 (MRS) signal ON........ NET operation mode
X12 (MRS) signal OFF........external operation mode