30
INVERTER SETTING
About setting
• Operation at an error occurrence
When the communication returns to normal within the time period set in
Pr.500
, the communication option error (E.OP1) does not occur.
• Operation after the time in
Pr.500
elapses after an error occurrence
When an error occurs, the inverter outputs a command to decelerate the motor or shuts off the output, and outputs the fault,
independently of the
Pr.500
setting.
Under position control, the operation is continued to the target position.
Fault description
Pr.502 setting
Operation
Indication
Fault output
Communication line
0
Continued
Normal
Not output
1, 11
2, 12
3
4
Communication option
0, 3
Output shutoff
"
E. 1
"
Provided
1, 2, 11, 12
Output to decelerate
and stop the motor
"
E. 1
"
after stop
Provided after stop
4
Continued
"CF" warning
Not output
Fault description
Pr.502 setting
Operation
Indication
Fault output
Communication line
0
Output shutoff
"
E.OP1
"
Provided
1, 11
Output to decelerate and
stop the motor
"
E.OP1
"
after stop
Provided after stop
2, 12
Not output
3
Continues operation with
the
Pr.779
Normal
4
"CF" warning
Communication option
itself
0, 3
Output stop status
continues.
"
E.1
"
kept
Kept provided
1, 2, 11, 12
4
Continued
"CF" warning
Not output