28
INVERTER SETTING
4.3 Operation at communication error occurrence
4.3.1
Operation selection at communication error occurrence (Pr.500 to Pr.502, Pr.779)
You can select operations at communication error occurrences by setting
Pr.500 to Pr.502, Pr.779
under network operation.
Waiting time for the communication line error output after a communication error
Waiting time for the communication error output after a communication line error occurrence can be set.
When a communication line error occurs and lasts longer than the time set in
Pr.500
, it is recognized as a communication error.
If the communication returns to normal within the time, it is not recognized as a communication error, and the operation
continues.
Pr.
Name
Setting range
Minimum setting
increments
Initial value
500
Communication error execution waiting time
0 to 999.8 s
0.1 s
0 s
Normal
Error
Pr.500
setting time
Normal
Error
Communication line status
Alarm signal (LF)
(
Pr.502
= 3 or 4)
Recognition
ON
Pr.500
setting time
Communication error
(E.OP1)