INVERTER SETTING
27
4
Operation mode cannot be directly changed between the PU operation mode and Network operation mode.
The
Pr.340
settings "2 or 12" are mainly used for communication operation using the inverter RS-485 terminal.
When a value other than "9999" (selection of automatic restart after instantaneous power failure) is set in
Pr.57 Restart coasting time
,
the inverter will resume the same operation state which was in before after power has been restored from an instantaneous power failure.
When
Pr.340
= "1 or 10", a start command turns off if power failure has occurred and then restored during a start command is on.
Switching between the PU and NET operation modes is available with the key on the operation panel or the X65 signal.
Refer to
for a switching method from the network.
10, 12
0
NET operation mode
Switching between the PU and NET operation mode is
enabled.
1
PU operation mode
Same as when
Pr.340
= "0"
2
NET operation mode
NET operation mode fixed
3, 4
External/PU combined operation mode
Same as when
Pr.340
= "0"
6
NET operation mode
Switching between the PU and NET operation mode is
enabled while running.
7
External operation mode
Same as when
Pr.340
= "0"
Pr.340
setting
Pr.79
setting
Operation mode at power ON or power
restoration
Operation mode switchover