60
7.2.2
Remote register (inverter (FR-A8NCE) to master module)
Remote register definition
Device
No.
Signal
Description
RWr0
Reply code
When "1" is set in RY21 or RY22, the following reply codes are set for the frequency setting
command. The setting value "0" is set normally, and a value other than "0" is set at an error.
RWr2
Reply code
When "1" is set in RY23 or RY24, the following reply codes are set for the torque command / torque
limit. The setting value "0" is set normally, and a value other than "0" is set at an error.
RWr4,
RWr5,
RWr6
Reply code
When the PID command (RWw4 to RWw6) is set, the following reply code is set for the PID
command. The setting value "0" is set normally, and a value other than "0" is set at an error.
Value
Description
H0000
Normal
H0001
Write mode fault
H0003
Setting range fault
Value
Description
H0000
Normal
H0003
Setting range fault
Value
Description
H0000
Normal
H0003
Setting range fault