94
OCH722A
12
SERVICE AND MAINTENANCE
(Continued to next page.)
Main remote controller screen
Parameters
Default
setting
Field
setting
Notes
Setting
Service
menu
Thermistor
adjustment
THW1
−10°C to +10°C
0°C
THW2
−10°C to +10°C
0°C
THW5A
−10°C to +10°C
0°C
THW5B
−10°C to +10°C
0°C
THW6
−10°C to +10°C
0°C
THW7
−10°C to +10°C
0°C
THW8
−10°C to +10°C
0°C
THW9
−10°C to +10°C
0°C
THW10
−10°C to +10°C
0°C
THWB1
−10°C to +10°C
0°C
Auxiliary settings
Economy settings for
pump.
On/Off *2
On
Delay (3 to 60 min)
10 min
Electric heater
(Heating)
Space heating: On (used)/Off (not used)
On
Electric heater delay timer (5 to 180 min)
30 min
Electric heater
(DHW)
Booster heater
DHW: On (used)/Off (not used)
On
Immersion heater DHW: On (used)/Off (not used)
On
Electric heater delay timer (15 to 30 min)
15 min
Mixing valve
control
Running (10 to 240 sec)
120 sec
Interval (1 to 30 min)
2 min
Flow sensor *10
Minimum (0 to 100L/min)
5 L/min
Maximum (0 to 100L/min)
100 L/min
Analog output
Interval (1 to 30 min)
5 min
Priority (Normal/High)
Normal
Pump speed
DHW
Pump speed (1 to 5)
5
Heating
Pump speed (1 to 5)
5
Heat source setting
Standard/Heater/Boiler/Hybrid *3
Standard
Heat pump settings
Heat pump flow rate
range
Minimum (0 to 100L/min)
5 L/min
Maximum (0 to 100L/min)
100 L/min
Quiet mode
Day (Mon to Sun)
—
Time
0:00-23:45
Quiet level (Normal/Level1/Level2)
Normal
Operation
settings
Heating
operation
*4
Flow temp.range
*6
Minimum.temp. (20 to 45°C)
30°C
Maximum.temp. (35 to 60°C)
50°C
Room temp.
control
*9
Mode (Normal/Fast)
Normal
Interval(10 to 60min)
10min
Heat pump
thermo diff.adjust
On/Off *2
On
Lower limit (−9 to −1°C)
-5°C
Upper limit (+3 to +5°C)
5°C
Freeze stat function *7
Outdoor ambient temp. (3 to 20°C) / **
5°C
Simultaneous operation (DHW/
Heating)
On/Off *2
Off
Outdoor ambient temp. (−30 to +10°C)
−15°C
Cold weather function
On/Off *2
Off
Outdoor ambient temp. (−30 to −10°C)
−15°C
Boiler operation
Hybrid settings
Outdoor ambient temp. (−30 to +10°C)
−15°C
Priority mode (Ambient/Cost/CO
2
)
Ambient
Intelligent set
-
tings
Energy
price *5
Electricity (0.001 to 999 */kWh)
0.5 */kWh
Boiler (0.001 to 999 */kWh)
0.5 */kWh
CO2
emission
Electricity
(0.001 to 999 kg -CO2/kWh)
0.5 kg -CO2/kWh
Boiler
(0.001 to 999 kg -CO2/kWh)
0.5 kg -CO2/kWh
Heat
source
Heat pump capacity (1 to 40 kW)
11.2 kW
Boiler efficiency (25 to 150%) 80%
Booster heater 1 capacity
(0 to 30 kW)
2 kW
Booster heater 2 capacity
(0 to 30 kW)
4 kW
Engineers Forms
Commissioning/Field settings record sheet (continued from the previous page)