Part Name
Checkpoints
3-way valve
(1) Check the movement of the red indicator. The red indicator normally points to A in DHW mode and to
B in Heating mode as shown to the left.
(2) If each indicator position is correct but the 3-way valve does not work properly, the motor may not fit
onto the valve securely, so remove the motor by pressing the release button, and reinstall it.
Thermistors
Thermistor (TH3)
<Liquid>
Thermistor (TH4)
<Discharge>
Thermistor (TH7)
<Ambient>
Thermistor (TH8)
<Heat sink>
Thermistor (TH32)
<Brine inlet>
Thermistor (TH33)
<Comp. surface>
Thermistor (TH34)
<Brine outlet>
Disconnect the connector then measure the resistance with a tester.
(At ambient temperatures of 10–30°C.)
Thermistor
Normal
Abnormal
TH1
4.3 – 9.5 kΩ
Open or short
TH2
TH3
4.3 – 9.6 kΩ
TH4
160 – 410 kΩ
TH7
4.3 – 9.6 kΩ
TH8
39 – 105 kΩ
TH32
4.3 – 9.6 kΩ
TH33
TH34
THW1
4.3 – 9.5 kΩ
THW2
THW5
THW6
THW7
THW8
THW9
THWB1
40 – 100 kΩ
Brine pump (MBP1)
Refer to the next page.
Motor for compressor
(MC)
Measure the resistance between the terminals with a tester. (Winding temperature 20°C)
Linear expansion valve
(LEV-A)
Disconnect the connector then measure the resistance with a tester. (Winding temperature 20°C)
58