Part Name
Checkpoints
Booster heater
Measure the resistance between the terminals with a tester.
Thermostat (90°C) and thermal cut out (121°C)
90 °C
Manual reset
water
thermostat
121 °C
Thermal
cut-out
AWG18
AWG18
9
10
Terminal
Normal
Abnormal
9–10
110(±35) mΩ
Open or Short
3 + 6 kW heater (400 V, 3 phase)
5
6
AWG13 FEP BLUE
AWG13 FEP BLUE
AWG15 FEP WHITE
2kW
4
AWG13 FEP BLUE
2kW
2kW
2
3
1kW
1
1kW
1kW
AWG15 FEP WHITE
AWG15 FEP WHITE
Terminal
Normal
Abnormal
1−2=2-3=1−3
105.8(+11.8/−5) Ω
Open or Short
4−5=5-6=4−6
52.9(+5.8/−2.5) Ω
Open or Short
Earth leakage circuit breaker for heater
If a short circuit occurs on the booster heater, immersion heater, or each power
line, a short-circuit breaker will trip and power source will be blocked.
Eliminate the causes of short circuit and then turn on the breaker again.
Relay for heater
R S T A1 A2
U V W
When the applied voltage is not 230 V AC across the terminals A1-A2, check
the terminals R-U, S-V, and T-W are open.
When the applied voltage is 230 V AC across the terminals A1-A2, check the
terminals R-U, S-V, and T-W are short.