<Display function of inspection for heat pump unit>
The blinking patterns of both LED1 (green) and LED2 (red) on controller circuit board indicate the types of abnormality when it
occurs. Types of abnormality can be indicated in details by connecting an optional part “A-Control Service Tool (PAC-SK52ST)”
to connector CNM on controller circuit board.
F5
—
—
—
E6
E7
—
—
E0
E3
E4
E5
[Display]
(1) Normal condition
(2) Abnormal condition
Unit condition
Controller circuit board
A-Control Service Tool
LED1 (Green)
LED2 (Red)
Check code
When the power is turned on
When unit stops
When compressor is warming up
When unit operates
Lighted
Lighted
Lighted
Lighted
Lighted
Not lighted
Indication of the display
Alternately blinking display
Operation mode
Not lighted
Lighted
00, etc.
08, etc.
C5, H7, etc.
Indication
Error
Check
code*
Controller circuit board
Contents
Inspection method
LED1 (Green) LED2 (Red)
1 blinking 2 blinking
2 blinking 1 blinking
2 blinking
3 blinking
4 blinking
5 blinking
Connector(63H) is open.
Startup time over
Check code is not defined.
Incorrect connection
Miswiring of FTC/Controller circuit board
connecting wire
Miswiring of FTC/Controller circuit
board connecting wire (converse
wiring or disconnection)
FTC/Controller circuit board communication error
(signal receiving error) is detected by indoor unit.
FTC/Controller circuit board communication error
(transmitting error) is detected by indoor unit.
FTC/Controller circuit board communication error
(signal receiving error) is detected by
outdoor unit.
FTC/Controller circuit board communication error
(transmitting error) is detected by outdoor unit.
Remote controller signal receiving
error is detected by remote controller.
Remote controller transmitting error
is detected by remote controller.
Remote controller signal receiving
error is detected by FTC.
Remote controller transmitting error
is detected by indoor FTCt.
Serial communication error
<Communication between outdoor
controller board and power outdoor
circuit board>
*
Check code displayed on remote controller
** Refer to service manual for indoor unit.
1
Check if FTC/Controller circuit board connecting wire is
connected correctly.
2
Check if noise entered into FTC/Controller circuit board
connecting wire or power supply.
3
Re-check error by turning off power, and on again.
1
Check if connector (63H) on the controller
board is not disconnected.
2
Check continuity of pressure switch (63H) by tester.
1
Check if connector (CN4) on controller circuit board and
outdoor power circuit board is not disconnected.
1
Connect I/F to the unit.
1
Check if noise entered into transmission wire of remote controller.
2
Check if noise entered into FTC/Controller circuit board connecting wire.
3
Re-check error by turning off power, and on again.
1
Check if connecting wire of FTC or remote controller
is connected correctly.
2
Check if noise entered into transmission wire of remote
controller.
3
Re-check error by turning off power, and on again.
1
Check if FTC/Controller circuit board connecting wire is connected correctly.
2
Check if noise entered into FTC/Controller circuit board connecting wire or
power supply.
3
Check if noise entered into FTC/Controller circuit board controller board.
4
Re-check error by turning off power, and on again.
—
P.45
—
(EA)
(Eb)
(EC)
**
**
(E8)
Detailed
reference
page
(E9)
P.43
P.44
P.43
P.44
—
—
—
Ed
EF
EE
(2) Abnormal condition
Indication
Error
Detailed
reference
page
Controller circuit board
Content
s
Check
code*
Inspection method
LED1 (Green) LED2 (Red)
1 blinking 2 blinking Connector(63H) is open.
F5
1
Check if connector (63H) on the controller
board is not disconnected.
2
Check continuity of pressure switch (63H) by
tester.
P46
2 blinking 1 blinking Miswiring of FTC/Controller circuit board
connecting wire
─
1
Check if FTC/Controller circuit board
connecting wire is connected correctly.
2
Check if noise entered into FTC/Controller
circuit board connecting wire or power supply.
3
Re-check error by turning off power, and on
again.
(EA)
Miswiring of FTC/Controller circuit
board connecting wire (converse
wiring or disconnection)
─
(Eb)
Startup time over
─
(EC)
2 blinking FTC/Controller circuit board communication
error (signal receiving error) is detected by
FTC.
E6
1
Check if FTC/Controller circuit board
connecting wire is connected correctly.
2
Check if noise entered into FTC/Controller
circuit board connecting wire or power supply.
3
Check if noise entered into FTC/Controller
circuit board.
4
Re-check error by turning off power, and on
again.
P.45
FTC/Controller circuit board communication
error (transmitting error) is detected by
FTC.
E7
P.45
FTC/Controller circuit board communication
error (signal receiving error) is detected by
controller circuit board.
─
(E8)
FTC/Controller circuit board communication
error (transmitting error) is detected by
controller circuit board.
─
(E9)
3 blinking Remote controller signal receiving
error is detected by remote controller.
E0
1
Check if connecting wire of FTC or remote
controller is connected correctly.
2
Check if noise entered into transmission wire
of remote controller.
3
Re-check error by turning off power, and on
again.
P.44
Remote controller transmitting error
is detected by remote controller.
E3
P.45
Remote controller signal receiving
error is detected by FTC.
E4
P.44
Remote controller transmitting error
is detected by indoor FTC.
E5
P.45
4 blinking Check code is not defined.
EF
1
Check if noise entered into transmission wire
of remote controller.
2
Check if noise entered into FTC/Controller
circuit board connecting wire.
3
Re-check error by turning off power, and on
again.
─
Incorrect connection
EE
1
Connect I/F to the unit.
─
5 blinking Serial communication error
<Communication between controller
circuit board and power circuit board>
Ed
1
Check if connector (CN4) on controller
circuit board and power circuit board is not
disconnected.
─